Plan Review Notes For Permit 20020040 |
Permit Number |
20020040 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-03-04 09:15:43 | 1) SHT. 3 OF 7 SHOWS THE MAIN DRAIN COVER AS 12 INCHES | | BY 12 INCHES BUT SHT. 4 SHOWS THE MAIN DRAIN COVER AS | | 18 INCHES BY 18 INCHES . THE MAIN DRAIN DETAIL ON SHT. | | 5 OF 7 SHOWS A 12 INCHES BY 12 INCHES GRATE. CLARIFY. | | 2) SUBMIT A PUMP CURVE THAT SHOWS THE DESIGN TDH. THE | | PUMP CURVE ON THE PLAN ONLY GOES TO 30 FT. TDH AND THE | | DESIGN IS BASED ON 60 FT. TDH. | | 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE POOL | | HEATER. WPB AMEND. TO FBC SEC. 105.1. | | 4) THE PLANS SHOW THE OVERFLOW DISCHARGE AND WASTE TO | | DISCHARGE TO THE CITY STORM SEWER. THIS IS PROHIBITED | | PER CODE OF CITY ORDINANCES ARTICLE V, SEC. 90-203 (A). | | PLEASE CONTACT MANNY GONZALEZ WITH THE CITY'S | | ENGINEERING DEPT. AT 561-494-1085 FOR FURTHER | | DIRECTION. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|