Plan Review Notes
Plan Review Notes For Permit 20011248
Permit Number 20011248
Review Stop P
Sequence Number 1
Notes
Date Text
2020-01-30 12:54:3201/30/20 1ST PLUMBING/BACKFLOW REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A GENERAL CONTRACTOR OR AN UNDERGROUND UTILITY AND
 EXCAVATION CONTRACTOR CANNOT INSTALL A BACKFLOW DEVICE
 PER THE 2019 FLORIDA STATUTES TITLE XXXII CHAPTER
 489.105(N). PLEASE PROVIDE THE PERMITTING DEPARTMENT
 WITH A VALID STATE OF FLORIDA LICENSED CONTRACTOR ALONG
 WITH AN APPLICATION.
  
 FS 489.105 DEFINITIONS.-- AS USED IN THIS PART:
 (1) "BOARD" MEANS THE CONSTRUCTION INDUSTRY LICENSING
 BOARD.
 (2) "DEPARTMENT" MEANS THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION.
 (3) "CONTRACTOR" MEANS THE PERSON WHO IS QUALIFIED FOR,
 AND IS ONLY RESPONSIBLE FOR, THE PROJECT.
  
 (N) "UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR"
 MEANS A CONTRACTOR WHOSE SERVICES ARE LIMITED TO THE
 CONSTRUCTION, INSTALLATION, AND REPAIR, ON PUBLIC OR
 PRIVATE PROPERTY, WHETHER ACCOMPLISHED THROUGH OPEN
 EXCAVATIONS OR THROUGH OTHER MEANS, INCLUDING, BUT NOT
 LIMITED TO, DIRECTIONAL DRILLING, AUGER BORING, JACKING
 AND BORING, TRENCHLESS TECHNOLOGIES, WET AND DRY TAPS,
 GROUTING, AND SLIP LINING, OF MAIN SANITARY SEWER
 COLLECTION SYSTEMS, MAIN WATER DISTRIBUTION SYSTEMS,
 STORM SEWER COLLECTION SYSTEMS, AND THE CONTINUATION OF
 UTILITY LINES FROM THE MAIN SYSTEMS TO A POINT OF
 TERMINATION UP TO AND INCLUDING THE METER LOCATION FOR
 THE INDIVIDUAL OCCUPANCY, SEWER COLLECTION SYSTEMS AT
 PROPERTY LINE ON RESIDENTIAL OR SINGLE-OCCUPANCY
 COMMERCIAL PROPERTIES, OR ON MULTIOCCUPANCY PROPERTIES
 AT MANHOLE OR WYE LATERAL EXTENDED TO AN INVERT
 ELEVATION AS ENGINEERED TO ACCOMMODATE FUTURE BUILDING
 SEWERS, WATER DISTRIBUTION SYSTEMS, OR STORM SEWER
 COLLECTION SYSTEMS AT STORM SEWER STRUCTURES. HOWEVER,
 AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY
 INSTALL EMPTY UNDERGROUND CONDUITS IN RIGHTS-OF-WAY,
 EASEMENTS, PLATTED RIGHTS-OF-WAY IN NEW SITE
 DEVELOPMENT, AND SLEEVES FOR PARKING LOT CROSSINGS NO
 SMALLER THAN 2 INCHES IN DIAMETER IF EACH CONDUIT
 SYSTEM INSTALLED IS DESIGNED BY A LICENSED PROFESSIONAL
 ENGINEER OR AN AUTHORIZED EMPLOYEE OF A MUNICIPALITY,
 COUNTY, OR PUBLIC UTILITY AND THE INSTALLATION OF SUCH
 CONDUIT DOES NOT INCLUDE INSTALLATION OF ANY CONDUCTOR
 WIRING OR CONNECTION TO AN ENERGIZED ELECTRICAL SYSTEM.
 AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY
 NOT INSTALL PIPING THAT IS AN INTEGRAL PART OF A FIRE
 PROTECTION SYSTEM AS DEFINED IN S. 633.102 BEGINNING AT
 THE POINT WHERE THE PIPING IS USED EXCLUSIVELY FOR SUCH
 SYSTEM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  
  