Plan Review Notes For Permit 20011223
Permit Number 20011223
Review Stop E
Sequence Number 2
Notes
Date Text
2020-10-20 17:19:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FEEDER OFF GENERATOR GOES INTO GEPD DOES THIS CONFORM
 TO 700.10? IF SO PLEASE EXPLAIN, SHOULD IT NOT BE IN
 SEPARATE VERTICAL SWITCHBOARD SECTIONS?