Date Text
2020-10-20 07:58:29NEW 8 STORY BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) THE WIND DESIGN DATA HAS BEEN REVISED ON THE
 STRUCTURAL DRAWINGS BUT NOT ON THE PROVIDED STRUCTURAL
 CALCULATIONS - PLEASE REVISE THE STRUCTURAL
 CALCULATIONS TO MATCH THE WIND DESIGN DATA SHOWN ON THE
 STRUCTURAL DRAWINGS.
  
 DEFERRED ITEMS ? TO BE REVIEWED AND MARKED APPROVED BY
 THE BUILDING DESIGNER OF RECORD AND REVIEWED BY THE
 BUILDING DIVISION PLAN REVIEW BEFORE INSTALLATION -
 1) EXTERIOR WINDOW, DOOR AND LOUVER PRODUCT APPROVALS.
 FBC 1609
 2) SHORING AND RESHORING PLANS. FBC 110.8.4.3
 3) GUARD RAILING. FBC 1607.8
 4) ROOFING SYSTEM PRODUCT APPROVALS. FBC 1609.5.2
 5) ROOF TOP EQUIPMENT SCREENING. FBC 1510.6
 6) POOL. FBC 454
 7) ACOUSTICAL TEST REPORTS FOR THE FLOOR/CEILING
 ASSEMBLIES IIC AND STC PER FBC 1207 AND FLAME SPREAD
 INDEX PER FBC 603.1
 8) TRELLIS DETAILS.
 9) METAL CANOPIES.
  
  