2020-07-21 10:08:11 | PLUMBING 1ST REVIEW COMMENTS:20011223 |
| 1) SHEET 5.10 KITCHEN WATER ISOMETRIC MISSING DOWN FEED |
| SHUT OFF VALVE. FBC-PLB 606.1 |
| 2) SHEET P6.1 SHOW A/C COND DISCHARGING INTO THE STORM. |
| PER CITY OF WEST PALM BEACH CITY ORD. |
| 3) SHEET 6.1 POOL MAKE UP WATER PER W.P.B CROSS |
| CONNECTION MANUAL MUST BE RPZ TYPE, LEAD FREE, AND |
| INSTALLED ONLY BY LICENSED PLUMBING CONTRACTOR. |
| 4) SHEET 6.1 BOOSTER PUMP WATER DETAIL SHOWS THE |
| EXPANSION VALVE AS TYPE WATTS 174A SET @ 100 PSI FOR |
| THERMO EXPANSION CONTROL. THIS DEVICE IS NOT APPROVED |
| AS A THERMO EXPANSION DEVISE FBC-PLB 607.3 AND MUST BE |
| SET AT A MAX PRESSURE OF 80 PSI. FBC-PLB 604.8 |
| 5) SHEET 6.1 POOL BACKWASH IS NOT PERMITTED TO |
| DISCHARGE INTO THE SANITARY SYSTEM PER W.P.B CITY ORD. |
| 6) SHEET 6.2 WATER HEATER PIPING DETAIL PLEASE SHOW |
| PIPE SIZE. FBC 107.2.1 |
| 7) COMMENT REMOVED |
| 8) BASE ON YOUR DESCRIPTION OF THIS PROJECT IT WOULD |
| SEEM TO ME THAT THIS WOULD BE A LONG TERM CARE FACILITY |
| WHICH REQUIRES 50% OF THE OCCUPIED ROOMS TO MEET |
| FLORIDA ACCESSIBILITY. FBC-ACC 223.4 |
| 9) MALE AND FEMALE RESTROOMS A123, A125 MUST HAVE 1 OF |
| EACH COMMON SINK MEET FLORIDA ACCESSIBILITY. FBC-ACC |
| 212.2. PLEASE SHOW THE REQUIRED CLEAR FLOOR SPACE. |
| 10) SHEET A2.1B BEAUTY SALON TEA/COFFEE SINK PLEASE |
| SHOW THE REQUIRED CLEAR FLOOR SPACE DETAIL. FBC-ACC |
| 212.2. |
| 11) SHEET A2.1B PANTRY B107 PLEASE SHOW THE REQUIRED |
| CLEAR FLOOR SPACE DETAIL. FBC-ACC 212.2. |
| 12) PLEASE SHOW ALL ROOM DIMENSIONS THAT CONTAIN |
| PLUMBING FIXTURES. WITHOUT I AM UNABLE TO VERIFY |
| FLORIDA ACCESSIBILITY CAN BE ACHIEVED. FBC 107.3.5 |
| 13) ALL ACCESSIBLE ROOMS SHOW ROLL IN SHOWERS. ROLL IN |
| SHOWERS ARE NOT PERMITTED UNTIL THE MIN TUBS/ TRANSFER |
| SHOWERS HAVE BEEN PROVIDED PER TABLE FBC-ACC 224.2. |
| 14) PLEASE CALL OUT TYPE A OR B SPEC FOR THE BATHING |
| UNITS. FHA 7.34. UNIT WITH 2 BATHING ROOM YOU ONLY SHOW |
| 1 PLEASE LIST THEM AS B SPEC. FBC 107.3.5 |
| 15) SHEET A2.6A UNITS WITH DOUBLE SINK HAVE BOTH A TUB |
| AND SHOWER BUT NOT WAY TO ACCESS THEM. PLEASE CLARIFY. |
| FBC 107.2.1 |
| 16) SHEET A2.4 YOU CALL OUT 154 TOTAL ROOM BUT ONLY 3 |
| ADA ROOMS. PLEASE CLARIFY. FBC 107.2.1 |
| 17) SHEET A 2.2A TOILET ROOM #A209 PLEASE SHOW THE |
| CLEAR FLOOR SPACE AND TURNING SPACE. FBC-ACC 603.2 |
| 18) SHEET A2.3 AND A307 APPEAR TO BE COMMON LAUNDRY |
| ROOMS. PLEASE PROVIDE THE REQUIRED CLEAR FLOOR SPACE |
| AND REACH RANGE DETAIL. FBC-ACC 611. |
| 19) SHEET A4.10 SHOWS A VERTICAL GRAB BAR. ALL GRAB |
| BARS SHALL BE INSTALLED IN THE HORIZONTAL POSITION. |
| FBC-ACC 609.4 |
| 20) SHEET A4.10 - A4.13 PROVIDE GRAB BAR DETAIL FOR |
| BOTH THE REAR AND SIDE GRAB BAR IN DETAIL # 3 AND 4. |
| FBC-ACC 604.5.1, 605.5.2 |
| 21) SHEET A4.10 - A4.13 SHOW MIRROR MOUNTING TO THE |
| BOTTOM OF THE REFLECTIVE SURFACE. FBC-ACC 603.3. |
| 22) SHEET A4.11 SHOW THE SHOWER VALVE BEING INSTALLED |
| MAX 48? OFF FINISHED FLOOR. FBC-ACC 608.5. |
| 23) SHEETS A4.14 - A4.17, A10.1, A10.2 , A10.4 SHOW THE |
| TOILET TO BE INSTALLED A MIN OF 18?. THIS WOULD BE |
| INCORRECT FOR BOTH FHA AND FLORIDA ACCESSIBILITY. FHA |
| DESIGN MANUAL REQUIRED 18? AS ABSOLUTE MEASUREMENT (FHA |
| 6.5) AND FLORIDA ACCESSIBILITY THIS WOULD BE THE MAX. |
| FBC-ACC 604.2 |
| 24) SHEETS A5.4 DETAIL # 1 AND 3 AND A5.6 SHOW THE GRAB |
| BARS AT BEING MOUNTED @ 36 TO THE CENTER. MAX ALLOWED |
| IS 36? TO THE TOP OF THE GRIPPING SURFACE. FBC-ACC |
| 609.4 |
| 25) SHEET A5.4 LOBBY REST ROOMS DO NOT APPEAR TO ME |
| POTTY PARITY. PLEASE CLARIFY. FBC-PLB 403.1.3. |
| 26) SEVERAL SHEETS EX. A103 HEADING IS LISTED AS |
| ACCESSIBILITY UNIT BUT SHOW FAIR HOUSING. PLEASE |
| CLARIFY FBC 107.2.1. |
| 27) SHEET A.103 DETAIL # IL-A2 IS SHOWING THE TOILET |
| ADJACENT TO THE SHOWER WHICH PER FHA 7.44 IS NOT |
| PERMITTED. |
| 28) SHEET A10.4 SHOWS WASHING MACHINE AS ACCESSIBLE |
| UNIT BUT APPEAR TO BE AN FHA UNIT. PLEASE CLARIFY. FBC |
| 107.2.1 |
| 29) SHEET A10.5 UNIT IL-C3 PLEASE PROVIDE THE CLEAR |
| FLOOR SPACE. |
| 30) SHEET A10.6 FOR ALL FHA UNITS WITH THE SHOWER |
| ACROSS FROM THE TOILETS PLEASE SHOW THE 48? X 56? CLEAR |
| FLOOR SPACE IS BEING ARCHIVED. FHA 7.44 |
| 31) PLEASE CLARIFY WHICH DESIGN SPEC YOUR DESIGN IS |
| BASED ON. IT APPEARS TO BE (B) BUT SHEET A10.7 UNIT |
| IL-C8 AND ALL UNITS SHOWN ON SHEET A10.8 ARE NOT LABEL |
| AT ALL. FBC 107.2.1 |
| 32) SHEET P2A THE MEN'S TOILET COMPARTMENT TOILET MUST |
| BE DIAGONAL OF THE DOOR. FBC-ACC 604.8.1.7. |
| 33)COMMENT REMOVED |
| 34) SHEET P2.2A AND A2.3A IS MISSING THE FLOOR DRAIN IN |
| THE LAUNDRY ROOM. FBC-PLB 412.4. |
| 35) SHEET P2.2A ROOM 214,215 SANITARY BRANCH THE COMBO |
| IS FACING THE WRONG WAY. FBC-PLB 706.3 |
| 36) SKY LOUNGE KITCHEN HAS 2 FIXTURES BEYOND THE VENT. |
| MUST ADD VENT BETWEEN F.S.K AND F.D. |
| 37) SHEET P4.3 UNIT 215 COMBO FITTING FACING WRONG |
| DIRECTION. FBC-PLB 412.4. |
| 38) SHEETS A4.1 THRU A4.8 APPEAR TO SHOW ADA ROLL IN |
| SHOWERS WITH SEAT. THE CONTROL WALL IS SHOWN AS ACROSS |
| FROM THE SEAT WHEN IT SHOULD BE WITH IN 27? OF THE SEAT |
| ON THE BACK WALL PER FBC-ACC 608.5.2. |
| 39) PLEASE SHOW THE PIPE SIZE ON THE PLUMBING ISOMETRIC |
| SHEET P5.1. FBC 107.3.5 |
| 40) SHEET P5.5 STACK # 5 SHOW THE KITCHEN DISCHARGING |
| INTO THE BATHROOM GROUP WET VENT. NO FIXTURES OTHER |
| THAN ANOTHER BATHROOM GROUP MAY DISCHARGE IN THIS WET |
| VENT. FBC-PLB 912.2.1 |
| |