2020-07-21 10:08:11PLUMBING 1ST REVIEW COMMENTS:20011223
 1) SHEET 5.10 KITCHEN WATER ISOMETRIC MISSING DOWN FEED
 SHUT OFF VALVE. FBC-PLB 606.1
 2) SHEET P6.1 SHOW A/C COND DISCHARGING INTO THE STORM.
 PER CITY OF WEST PALM BEACH CITY ORD.
 3) SHEET 6.1 POOL MAKE UP WATER PER W.P.B CROSS
 CONNECTION MANUAL MUST BE RPZ TYPE, LEAD FREE, AND
 INSTALLED ONLY BY LICENSED PLUMBING CONTRACTOR.
 4) SHEET 6.1 BOOSTER PUMP WATER DETAIL SHOWS THE
 EXPANSION VALVE AS TYPE WATTS 174A SET @ 100 PSI FOR
 THERMO EXPANSION CONTROL. THIS DEVICE IS NOT APPROVED
 AS A THERMO EXPANSION DEVISE FBC-PLB 607.3 AND MUST BE
 SET AT A MAX PRESSURE OF 80 PSI. FBC-PLB 604.8
 5) SHEET 6.1 POOL BACKWASH IS NOT PERMITTED TO
 DISCHARGE INTO THE SANITARY SYSTEM PER W.P.B CITY ORD.
 6) SHEET 6.2 WATER HEATER PIPING DETAIL PLEASE SHOW
 PIPE SIZE. FBC 107.2.1
 7) COMMENT REMOVED
 8) BASE ON YOUR DESCRIPTION OF THIS PROJECT IT WOULD
 SEEM TO ME THAT THIS WOULD BE A LONG TERM CARE FACILITY
 WHICH REQUIRES 50% OF THE OCCUPIED ROOMS TO MEET
 FLORIDA ACCESSIBILITY. FBC-ACC 223.4
 9) MALE AND FEMALE RESTROOMS A123, A125 MUST HAVE 1 OF
 EACH COMMON SINK MEET FLORIDA ACCESSIBILITY. FBC-ACC
 212.2. PLEASE SHOW THE REQUIRED CLEAR FLOOR SPACE.
 10) SHEET A2.1B BEAUTY SALON TEA/COFFEE SINK PLEASE
 SHOW THE REQUIRED CLEAR FLOOR SPACE DETAIL. FBC-ACC
 212.2.
 11) SHEET A2.1B PANTRY B107 PLEASE SHOW THE REQUIRED
 CLEAR FLOOR SPACE DETAIL. FBC-ACC 212.2.
 12) PLEASE SHOW ALL ROOM DIMENSIONS THAT CONTAIN
 PLUMBING FIXTURES. WITHOUT I AM UNABLE TO VERIFY
 FLORIDA ACCESSIBILITY CAN BE ACHIEVED. FBC 107.3.5
 13) ALL ACCESSIBLE ROOMS SHOW ROLL IN SHOWERS. ROLL IN
 SHOWERS ARE NOT PERMITTED UNTIL THE MIN TUBS/ TRANSFER
 SHOWERS HAVE BEEN PROVIDED PER TABLE FBC-ACC 224.2.
 14) PLEASE CALL OUT TYPE A OR B SPEC FOR THE BATHING
 UNITS. FHA 7.34. UNIT WITH 2 BATHING ROOM YOU ONLY SHOW
 1 PLEASE LIST THEM AS B SPEC. FBC 107.3.5
 15) SHEET A2.6A UNITS WITH DOUBLE SINK HAVE BOTH A TUB
 AND SHOWER BUT NOT WAY TO ACCESS THEM. PLEASE CLARIFY.
 FBC 107.2.1
 16) SHEET A2.4 YOU CALL OUT 154 TOTAL ROOM BUT ONLY 3
 ADA ROOMS. PLEASE CLARIFY. FBC 107.2.1
 17) SHEET A 2.2A TOILET ROOM #A209 PLEASE SHOW THE
 CLEAR FLOOR SPACE AND TURNING SPACE. FBC-ACC 603.2
 18) SHEET A2.3 AND A307 APPEAR TO BE COMMON LAUNDRY
 ROOMS. PLEASE PROVIDE THE REQUIRED CLEAR FLOOR SPACE
 AND REACH RANGE DETAIL. FBC-ACC 611.
 19) SHEET A4.10 SHOWS A VERTICAL GRAB BAR. ALL GRAB
 BARS SHALL BE INSTALLED IN THE HORIZONTAL POSITION.
 FBC-ACC 609.4
 20) SHEET A4.10 - A4.13 PROVIDE GRAB BAR DETAIL FOR
 BOTH THE REAR AND SIDE GRAB BAR IN DETAIL # 3 AND 4.
 FBC-ACC 604.5.1, 605.5.2
 21) SHEET A4.10 - A4.13 SHOW MIRROR MOUNTING TO THE
 BOTTOM OF THE REFLECTIVE SURFACE. FBC-ACC 603.3.
 22) SHEET A4.11 SHOW THE SHOWER VALVE BEING INSTALLED
 MAX 48? OFF FINISHED FLOOR. FBC-ACC 608.5.
 23) SHEETS A4.14 - A4.17, A10.1, A10.2 , A10.4 SHOW THE
 TOILET TO BE INSTALLED A MIN OF 18?. THIS WOULD BE
 INCORRECT FOR BOTH FHA AND FLORIDA ACCESSIBILITY. FHA
 DESIGN MANUAL REQUIRED 18? AS ABSOLUTE MEASUREMENT (FHA
 6.5) AND FLORIDA ACCESSIBILITY THIS WOULD BE THE MAX.
 FBC-ACC 604.2
 24) SHEETS A5.4 DETAIL # 1 AND 3 AND A5.6 SHOW THE GRAB
 BARS AT BEING MOUNTED @ 36 TO THE CENTER. MAX ALLOWED
 IS 36? TO THE TOP OF THE GRIPPING SURFACE. FBC-ACC
 609.4
 25) SHEET A5.4 LOBBY REST ROOMS DO NOT APPEAR TO ME
 POTTY PARITY. PLEASE CLARIFY. FBC-PLB 403.1.3.
 26) SEVERAL SHEETS EX. A103 HEADING IS LISTED AS
 ACCESSIBILITY UNIT BUT SHOW FAIR HOUSING. PLEASE
 CLARIFY FBC 107.2.1.
 27) SHEET A.103 DETAIL # IL-A2 IS SHOWING THE TOILET
 ADJACENT TO THE SHOWER WHICH PER FHA 7.44 IS NOT
 PERMITTED.
 28) SHEET A10.4 SHOWS WASHING MACHINE AS ACCESSIBLE
 UNIT BUT APPEAR TO BE AN FHA UNIT. PLEASE CLARIFY. FBC
 107.2.1
 29) SHEET A10.5 UNIT IL-C3 PLEASE PROVIDE THE CLEAR
 FLOOR SPACE.
 30) SHEET A10.6 FOR ALL FHA UNITS WITH THE SHOWER
 ACROSS FROM THE TOILETS PLEASE SHOW THE 48? X 56? CLEAR
 FLOOR SPACE IS BEING ARCHIVED. FHA 7.44
 31) PLEASE CLARIFY WHICH DESIGN SPEC YOUR DESIGN IS
 BASED ON. IT APPEARS TO BE (B) BUT SHEET A10.7 UNIT
 IL-C8 AND ALL UNITS SHOWN ON SHEET A10.8 ARE NOT LABEL
 AT ALL. FBC 107.2.1
 32) SHEET P2A THE MEN'S TOILET COMPARTMENT TOILET MUST
 BE DIAGONAL OF THE DOOR. FBC-ACC 604.8.1.7.
 33)COMMENT REMOVED
 34) SHEET P2.2A AND A2.3A IS MISSING THE FLOOR DRAIN IN
 THE LAUNDRY ROOM. FBC-PLB 412.4.
 35) SHEET P2.2A ROOM 214,215 SANITARY BRANCH THE COMBO
 IS FACING THE WRONG WAY. FBC-PLB 706.3
 36) SKY LOUNGE KITCHEN HAS 2 FIXTURES BEYOND THE VENT.
 MUST ADD VENT BETWEEN F.S.K AND F.D.
 37) SHEET P4.3 UNIT 215 COMBO FITTING FACING WRONG
 DIRECTION. FBC-PLB 412.4.
 38) SHEETS A4.1 THRU A4.8 APPEAR TO SHOW ADA ROLL IN
 SHOWERS WITH SEAT. THE CONTROL WALL IS SHOWN AS ACROSS
 FROM THE SEAT WHEN IT SHOULD BE WITH IN 27? OF THE SEAT
 ON THE BACK WALL PER FBC-ACC 608.5.2.
 39) PLEASE SHOW THE PIPE SIZE ON THE PLUMBING ISOMETRIC
 SHEET P5.1. FBC 107.3.5
 40) SHEET P5.5 STACK # 5 SHOW THE KITCHEN DISCHARGING
 INTO THE BATHROOM GROUP WET VENT. NO FIXTURES OTHER
 THAN ANOTHER BATHROOM GROUP MAY DISCHARGE IN THIS WET
 VENT. FBC-PLB 912.2.1
  
 TIM HUNT