2020-08-17 16:04:56 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20011223 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| |
| 1) PLEASE SHOW RATED WALLS ON ALL OF THE MECHANICAL |
| SHEETS. FBC FS 107.2.1 |
| |
| 2) SHEET LS-0.0 THE ENERGY CALCULATIONS PRESENTED IN |
| THIS PACKAGE IS FOR MULTI-FAMILY. PLEASE SPECIFY EACH |
| OCCUPANCY BASED ON THE FBC CHAPTER 3. |
| |
| 3) PLEASE PROVIDE ENERGY CALCULATIONS FOR EACH OF THE |
| OCCUPANCY CLASSIFICATIONS. FBC EC 403 |
| |
| 4) IN THE R-2 OCCUPANCIES PLEASE SHOW WHICH METHOD IS |
| USED FOR VENTILATION; NATURAL OR MECHANICAL. PROVIDE |
| CALCULATIONS FOR THE ONE THAT IS USED. FBC M CHAPTER 4 |
| |
| 5) PLEASE REMOVE THE NOTE AT THE BOTTOM LEFT OF THE |
| MECHANICAL SHEETS AS THESE SHOULD BE CONSTRUCTION |
| DOCUMENTS NOT FOR INITIAL PERMIT REVIEW. FBC FS 107.2.1 |
| |
| 6) PLEASE PROVIDE DUCT GRILL SIZES FOR ALL SHEETS. FBC |
| FS 107.2.1 |
| |
| 7) PLEASE PROVIDE RETURN AIR TRANSFER SIZES IN ALL |
| LIVING QUARTERS. FBC FS 107.2.1 |
| |
| 8) SHEET M-6.4: VENTILATION EQUIPMENT SCHEDULE (TOP |
| CHART) SHOWS 6 NOTES. NOTE 6 HAS BEEN LEFT BLANK. |
| PLEASE SHOW THE NOTE OR IF THERE IS NO NOTE REMOVE THE |
| NUMBER 6. FBC FS 107.2.1 |
| |
| |
| 9) SHEET M-6.5 SHOWS OUTSIDE AIR CALCULATIONS FOR |
| (RESIDENTIAL) ENERGY CALCULATIONS INDICATES 0 CFM |
| OUTSIDE AIR FOR (SENIOR UNITS) PLEASE BE CONSISTENT ON |
| BOTH. FBC FS 107.2.1 |
| |
| 10) SHEET M-6.4 DESIGNATES OUTSIDE AIR CALCULATIONS FOR |
| THIS BUILDING. PLEASE REFLECT THESE CALCULATIONS ON THE |
| ENERGY CALCULATIONS SUBMITTED, SEVERAL AREAS INDICATE 0 |
| CFM OUTSIDE AIR. FBC M 401. |
| |
| 11) PLEASE SHOW HOW YOU ARE PROVIDING OUTDOOR AIR FOR |
| ALL LOUNGES. FBC M 401 |
| |
| |
| 12) PLEASE PROVIDE CALCULATIONS AND WAY NATURAL |
| VENTILATION IS PROVIDED ON ALL AREAS THAT ARE USING |
| NATURAL VENTILATION. FBC M 402 |
| |
| |
| 13) SHEET M-5.1 DRAWING 1- PLEASE PROVIDE THE TYPE OF |
| MATERIAL USED FOR THE A/C CONDENSATE DRAIN PIPE IN THIS |
| PLENUM AREA. FBC M 602.2.1 |
| |
| |
| 14) SHEET M-5.1 DRAWING 8- PLEASE PROVE THE SIGNED AND |
| SEALED DRAWINGS FOR THE ELEVATOR SHAFT RELIEF LOUVER. |
| FBC FS 107.2.1 |
| |
| 15) SHEET M-5.1 DRAWING 3- PLEASE SHOW HOW THIS X-VENT |
| FOR A DRYER DUCT MEETS- FBC M 504.4 FOR NO SCREENS AT |
| DUCT TERMINATION AND THE WAY THIS APPEARS TO OPEN FROM |
| THE MIDDLE, HOW THE BACKDRAFT DAMPER WILL NOT GATHER |
| LINT. |
| |
| |
| 16) SHEET M-5.1: DRAWING (2) INDICATES A FRESH AIR DUCT |
| RAN INTO THE MECHANICAL CLOSETS OF THE APARTMENTS. |
| PLEASE SHOW THESE, THE CEILING ACCESS PANEL AND THE |
| OUTDOOR AIR TERMINATION ON THE EXTERIOR OF THE |
| BUILDING, ON ALL THE UNIT DRAWINGS THAT ARE GOING TO |
| HAVE THESE INSTALLED. FBC FS 107.2.1 |
| |
| 17) PROVIDE A COPY OF THE INSTALLATION INSTRUCTIONS FOR |
| THE MAKE AND MODEL OF THE DRYER FOR EVERY RESIDENTIAL |
| DRYER WITH AN EXHAUST DUCT LENGTH OVER 35?. FBC M |
| 504.8.4.2 |
| |
| |
| 18) WHERE THE DRYER EXHAUST DUCT EQUIVALENT LENGTH |
| EXCEEDS 35? THE EQUIVALENT LENGTH OF THE DUCT SHALL BE |
| IDENTIFIED ON A PERMANENT LABEL OR TAG. THE LABEL OR |
| TAG SHALL BE LOCATED WITHIN 6? OF THE EXHAUST DUCT |
| CONNECTION. FBC M 504.8.5 |
| |
| 19) PLEASE SHOW KITCHEN VENTILATION FOR ALL DWELLING |
| UNITS THAT ARE PROVIDED WITH A KITCHEN. FBC M TABLE |
| 403.3.1.1 |
| |
| |
| 20) SHEET M-4.3 PLEASE SHOW THE RETURN PATH TO THE |
| AHU?S THROUGH THE DOOR OF THE MECHANICAL CLOSETS. FBC M |
| 601.6 |
| |
| 21) SHEET M-4.3 UNIT IL-A4- PLEASE SHOW THE RETURN AIR |
| PATH FROM MASTER BEDROOM. FBC M 601.6 |
| |
| 22) SHEET M-4.3 PLEASE PROVIDE THE DISTANCE FROM THE |
| COOKING APPLIANCE AND THE RETURN AIR OPENINGS. FBC M |
| 601.5 |
| |
| |
| 23) M-4. SHEETS. PLEASE SHOW HOW YOU ARE PROVIDING |
| MAKE-UP AIR FOR THE DRYER. FBC M 504.6 |
| |
| 24) M-4. SHEETS- PLEASE SHOW THE ENTIRE DRYER DUCT IN |
| THE APARTMENTS GOING FROM DRYER TO TERMINATION, THEY |
| APPEAR TO STOP AT THE BATH EXHAUST DUCT. FBC FS 107.2.1 |
| |
| |
| 25) ON THE UNIT DRAWINGS THERE ARE UNITS THAT HAVE A |
| TOILET ROOM ENCLOSED IN THE BATHROOM, PLEASE PROVIDE |
| BATHROOM EXHAUST IN THE BATHROOM ALSO. FBC M BATHROOM |
| DEFINITION; FBC M TABLE 4.3.3.1.1 |
| |
| 26) SHEET M-4.SHEETS- PLEASE SHOW THAT THE EXHAUST |
| TERMINATIONS ARE A MINIMUM OF 3? FROM OPERABLE OPENINGS |
| INTO THE UNIT. FBC M 501.3.1 (3) |
| |
| 27) SHEET M-4.7: UNIT IL-D1- PLEASE SHOW THE RETURN |
| PATH FOR THE DEN. FBC FS 107.2.1 |
| |
| 28) SHEET M-2.5B: PLEASE REMOVE ALL CLOUDS FROM SHEETS |
| AS THIS IS A 1ST CYCLE REVIEW. FBC FS 107.2.1 |
| |
| 29) SHEET M-2.5B: PLEASE SHOW HOW CORRIDOR AT W BATH |
| B505 AND M BATH B504 IS VENTILATED. FBC M TABLE |
| 403.3.1.1 |
| |
| 30) SHEET M-2.5B : PLEASE SHOW AND IDENTIFY THE EXHAUST |
| FANS IN THE MENS AND WOMENS BATHROOMS. FBC FS 107.2.1 |
| |
| |
| 31) SHEET M-7.1 VENTILATION RISER DIAGRAM CFM?S DO NOT |
| MATCH BLDG. PLAN LEVEL SHEETS. EXAMPLES ARE- PLEASE |
| CHECK THE CFM?S OF THE ACS AT EACH FLOOR. ACS-2 SHOWS |
| 650 CFM PER FLOOR. SHEETS M-2.6A AND M-2.6B SHOWS ONLY |
| 400 CFM PER FLOOR. ACS-3 SHOWS 550 FOR EACH FLOOR, |
| BLDG.. PLAN LEVEL SHEETS SHOW 370 CFM. FBC FS 1.7.2.1 |
| |
| 32) IDENTIFY EACH MAU RISER ON EACH FLOOR AT THE SHAFT |
| WHERE IT ENTERS THE FLOOR. FBC FS 107.2.1 |
| |
| 33) SHEET M-2.3.1: THE STORAGE ROOM IS ACCESSED THROUGH |
| THE PARKING GARAGE. PLEASE PROVIDE A FD FOR THE DUCT |
| WORK PENETRATING THE RATED WALL AT CORRIDOR AND STORAGE |
| ROOM. FBC FS 107.2.1 |
| |
| 34) PLEASE LABEL WASHERS AND DRYERS IN EACH LAUNDRY |
| AREA TO PROVIDE A COUNT OF EACH. FBC FS 107.2.1 |
| |
| 35) PROVIDE CLOTHES DRYER SPECS AND DUCT SIZES FOR |
| EACH, ALONG WITH DEVELOPED LENGTH AND TERMINATION |
| LOCATION FOR ALL LAUNDRY ROOMS. FBC FS 107.2.1 |
| |
| 36) PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL |
| DRYERS IN THE LAUNDRY ROOMS. FBC FS 107.2.1 |
| |
| 37) IN ALL ROOMS WITH FCU?S PLEASE PROVIDE OUTDOOR AIR |
| CFM?S BEING SUPPLIED TO EACH UNIT ON THE DRAWINGS. FBC |
| FS 107.2.1 |
| |
| 38) PLEASE PROVIDE A DETAIL DRAWING SHOWING THE KEF |
| TERMINATIONS ON THE EXTERIOR OF THE BUILDING. FBC M |
| 506.3.13 |
| |
| 39) PLEASE SHOW DISTANCE FROM PROPERTY LINES FOR ALL |
| HOOD TERMINATIONS. FBC M 506.3.13.3 |
| |
| 40) KITCHEN HOODS WILL REQUIRE A SEPARATE PERMIT AND |
| REVIEW. FBC FS 107.2.1 |
| |
| 41) SHEET M-2.2A: HOW ARE YOU PROVIDING MAKE-UP AIR FOR |
| THE HOODS? FBC FS M 508.1 |
| |
| 42) PLEASE PROVIDE AN AIR BALANCE REPORT FOR THIS |
| STRUCTURE. FBC M 508.1.2 |
| |
| 43) PLEASE PROVIDE KITCHEN EQUIPMENT INFORMATION AND |
| LOCATIONS. FBC FS 107.2.1 |
| |
| 44) SHEET M-2.1A: PLEASE SHOW BATH EXHAUST FAN AND DUCT |
| WORK TO TERMINATION FOR BATHROOM BEHIND PREPARATION |
| KITCHEN. FBC FS 107.2.1 |
| |
| 45) PLEASE EXPLAIN WHAT TEF-A IS EXHAUSTING AND |
| IDENTIFY THE ROOM IT IS LOCATED IN. FBC FS 107.2.1 |
| |
| 46) PLEASE SHOW THE RATED DAMPER AT THE RATED WALL |
| DIVIDING THE SMOKE COMPARTMENTS. FBC FS 107.2.1 |
| |
| 47) SHEET M-2.1A PROVIDE SPECS FOR THE HORIZONTAL MAU. |
| NOTE 11 STATES TO LOOK AT THE ROOF PLANS FOR LOCATION |
| OF THE REMOTE AIR COOLED CONDENSING UNITS. PLEASE |
| IDENTIFY EACH FOR THE MAU IT IS IDENTIFIED WITH. FBC FS |
| 107.2.1 |
| |
| 48) IT APPEARS THAT YOU HAVE FD?S IN GREASE DUCT AT |
| RATED WALL PENETRATIONS, PLEASE REMOVE ALL FD?S IN THE |
| GREASE DUCT AND SHOW HOW YOU WILL PROTECT THE |
| PENETRATIONS AS FD?S ARE NOT ALLOWED IN GREASE DUCTS. |
| FBC M 506.3.11 |
| |
| 49) THERE WILL BE A SEPARATE PERMIT AND REVIEW FOR ALL |
| OF THE REFRIGERATION SYSTEMS. FBC FS 107.2.1 |
| |
| 50) PLEASE SHOW HOW KEF-1 AND KEF-3 COMPLY WITH FBC M |
| 506.5.1.2 IN-LINE FAN LOCATION. |
| |
| 51) PLEASE SHOW THE CLEANOUTS FOR THE INLINE FANS FOR |
| KEF-1 AND KEF-3. FBC M 506.3.8.2 |
| |
| 52) PLEASE SHOW GREASE DUCT CLEANOUT LOCATIONS. FBC M |
| 506.3.8 |
| |
| 53) PLEASE PROVIDE SPECS FOR COMMERCIAL LAUNDRY |
| EQUIPMENT. FBC FS 107.2.1 |
| |
| 54) PLEASE IDENTIFY LAUNDRY EQUIPMENT ON PLANS. FBC FS |
| 107.2.1 |
| |
| 55) PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR |
| COMMERCIAL DRYERS AND O.A. LOUVER. FBC FG CHAPTER 4. |
| |
| 56) SHEET M-2.A THE WALLS OF THE LAUNDRY ROOM ARE |
| RATED, PLEASE SHOW HOW ALL THE DUCT PENETRATIONS MEET |
| FBC M 607.5.3 |
| |
| 57) IN THE GRAND FOYER THERE IS A LABEL BAR/GRILL, IS |
| THERE ANY COOKING BEING DONE IN THIS AREA? FBC FS |
| 107.2.1 |
| |
| 58) PLEASE PROVIDE SPEC SHEETS FOR GENERATOR. FBC FS |
| 107.2.1 |
| |
| 59) THE GENERATOR MUST BE UNDER A SEPARATE PERMIT AND |
| REVIEW. FBC FS 107.2.1 |
| |
| 60) PLEASE PROVIDE A DETAIL DRAWING OF THE GENERATOR |
| ROOM ALONG WITH VENTILATION CALCULATIONS TO VERIFY |
| LOUVER SIZES. FBC FS 107.2.1 |
| |
| 61) PLEASE SHOW THE GENERATOR EXHAUST PIPING AND |
| TERMINATION. FBC FS 107.2.1 |
| |
| 62) PLEASE EXPLAIN THE INTENT OF EF-4 AND THE 14?X14? |
| DUCT WORK IN THE GENERATOR ROOM. FBC FS 107.2.1 |
| |
| 63) PLEASE PROVIDE SPECS FOR ALL EQUIPMENT IN THE |
| BOILER ROOM. FBC FS 107.2.1 |
| |
| 64) SHEET M-2.1B: NOTE (5) STATES THIS LOUVER IS AN OUT |
| DOOR AIR TO AHU/ FCU RETURN. THIS LOUVER IS LOCATED |
| INSIDE THE ENTRANCE OF THE PARKING GARAGE. PLEASE SHOW |
| THIS LOUVER AT THE EXTERIOR OF THE BUILDING. FBC FS |
| 107.2.1 |
| |
| 65) SHEET M-2.1B: O/A LOUVER FOR AHU-OFF IS LOCATED IN |
| THE PARKING GARAGE, THIS CANNOT BE LOCATED IN THIS |
| AREA. PLEASE MOVE THE O/A LOUVER TO THE EXTERIOR OF THE |
| BUILDING. FBC FS 107.2.1 |
| |
| 66) PLEASE PROVIDE DETAILS FOR THE BEAUTY SALON, PLEASE |
| SHOW IT MEETS FBC M TABLE 403.3.1.1 FOR VENTILATION AND |
| FOOTNOTES (B & H). |
| |
| 67) SHEETS M2.1A AND M2.1B: ACCORDING TO SHEET LS-0.1 |
| THERE ARE SEVERAL RATED WALLS ON THIS FLOOR. PLEASE |
| SHOW THE REQUIRED FD FOR EACH DUCT PENETRATION. FBC M |
| 607.5.3 |
| |
| 68) THERE ARE SEVERAL (MEP CLOSETS) ON THIS 1ST FLOOR. |
| ACCORDING TO SHEET LS-0.1 THESE CLOSETS ARE 1 HR. RATED |
| FIRE PARTITIONS, PLEASE SHOW FD IN EACH PENETRATION OF |
| THESE RATED WALLS. FBC M 607.5.3 |
| |
| 69) PLEASE PROVIDE DETAIL DRAWINGS AND CALCULATIONS |
| THAT SHOW THE PARKING GARAGE IS AN OPEN GARAGE. FBC FS |
| 107.3.2 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |