2020-07-21 10:09:23GAS 1ST REVIEW COMMENTS:20011223
 1) SUBMIT WHICH OF THE APPLICABLE SIZING TABLES USED TO
 SIZE THE GAS SYSTEM AFTER THE PRESSURE REGULATORS OR
 PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH
 SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD
 THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER
 TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND
 TABLES 402.4 (1) THRU 402.4 (37)
 2) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4
 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1
 4) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 5) DISCOVERY ROOM B116 PROVIDE MAKE UP AIR. SUBMIT
 CALCULATIONS FOR COMBUSTION AIR PER THE 2017 FBC-FUEL
 GAS CODE SEC.304.1,
  
  
 TIM HUNT
 CITY OF WEST PALM BEACH ( CAP GOVERNMENT)
 [email protected]
  
  
  