Plan Review Notes For Permit 20011223 |
Permit Number |
20011223 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-07-21 10:09:23 | GAS 1ST REVIEW COMMENTS:20011223 | | 1) SUBMIT WHICH OF THE APPLICABLE SIZING TABLES USED TO | | SIZE THE GAS SYSTEM AFTER THE PRESSURE REGULATORS OR | | PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH | | SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD | | THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER | | TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND | | TABLES 402.4 (1) THRU 402.4 (37) | | 2) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4 | | 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | INSTALLATION. 2014 FGC SEC.410.1 | | 4) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE | | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 | | 5) DISCOVERY ROOM B116 PROVIDE MAKE UP AIR. SUBMIT | | CALCULATIONS FOR COMBUSTION AIR PER THE 2017 FBC-FUEL | | GAS CODE SEC.304.1, | | | | | | TIM HUNT | | CITY OF WEST PALM BEACH ( CAP GOVERNMENT) | | [email protected] | | | | | | |
|