2020-07-20 12:09:29 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PLANS ARE LABELED AS NOT FOR CONSTRUCTION. TO BE |
| USED FOR PERMIT THE PLANS MUST BE 100% COMPLETE AND |
| THIS STATEMENT MUST NOT BE PRESENT. PROVIDE CORRECTION. |
| WPB FBC 105.1, 107.2.1 |
| 2. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING |
| PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK |
| IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY |
| OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1 |
| 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| SERVICE AND DOWNSTREAM PANELS, INCLUDING INFORMATION |
| FROM THE POWER COMPANY, STATING WHAT THE AVAILABLE |
| SHORT CIRCUIT CURRENT IS FOR THE SERVICE AND DOWNSTREAM |
| PANELS TO CONFIRM THE STATED AIC RATING OF THE |
| ELECTRICAL EQUIPMENT IS ADEQUATE. CALCULATIONS SHOULD |
| BE PERFORMED UNTIL THEY REACH BELOW 10,000 AIC. NEC |
| 110.9, 110.10 |
| 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| 5. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| FBC EC C405.1, R404.1 |
| 6. PROVIDE VOLTAGE DROP CALCULATIONS TO COMPLY WITH |
| CODE. FBC EC C405.6.3 |
| 7. PROVIDE ENCLOSURE FOR POOL PANEL ADEQUATE FOR THE |
| ENVIRONMENT. NEC TABLE 110.28 |
| 8. IT APPEARS THAT NEC 220.84 WAS USED FOR CALCULATIONS |
| FOR ALL RESIDENTIAL SERVICES. THIS METHOD IS PERMITTED |
| ONLY WHERE THE UNITS ARE EQUIPPED WITH ELECTRIC COOKING |
| EQUIPMENT. THIS IS NOT THE CASE FOR ALL UNITS. PROVIDE |
| ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. NEC |
| 220.84 |
| 9. PROVIDE ACCURATE LOAD CALCULATION AND PANEL SCHEDULE |
| FOR PANEL GEDP. WHAT WILL THE LOAD ON THE GENERATOR BE? |
| NEC 220 |
| 10. PROVIDE DETAILS OF COMPLIANCE WITH THE EMERGENCY |
| ENVIRONMENTAL CONTROL REQUIRED PER FLORIDA |
| ADMINISTRATIVE CODE, RULE 58A-5.036 |
| 11. SHEET E-7.2 STATES THE GENERATOR DESIGN IS BASED ON |
| NEC 702, WHICH IS FOR OPTIONAL STANDBY SYSTEMS. THIS IS |
| A LEGALLY REQUIRED SYSTEM. PROVIDE CLARIFICATION AND/OR |
| CORRECTIONS. NEC 701.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| |