2020-07-20 12:09:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLANS ARE LABELED AS NOT FOR CONSTRUCTION. TO BE
 USED FOR PERMIT THE PLANS MUST BE 100% COMPLETE AND
 THIS STATEMENT MUST NOT BE PRESENT. PROVIDE CORRECTION.
 WPB FBC 105.1, 107.2.1
 2. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE AND DOWNSTREAM PANELS, INCLUDING INFORMATION
 FROM THE POWER COMPANY, STATING WHAT THE AVAILABLE
 SHORT CIRCUIT CURRENT IS FOR THE SERVICE AND DOWNSTREAM
 PANELS TO CONFIRM THE STATED AIC RATING OF THE
 ELECTRICAL EQUIPMENT IS ADEQUATE. CALCULATIONS SHOULD
 BE PERFORMED UNTIL THEY REACH BELOW 10,000 AIC. NEC
 110.9, 110.10
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 5. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 6. PROVIDE VOLTAGE DROP CALCULATIONS TO COMPLY WITH
 CODE. FBC EC C405.6.3
 7. PROVIDE ENCLOSURE FOR POOL PANEL ADEQUATE FOR THE
 ENVIRONMENT. NEC TABLE 110.28
 8. IT APPEARS THAT NEC 220.84 WAS USED FOR CALCULATIONS
 FOR ALL RESIDENTIAL SERVICES. THIS METHOD IS PERMITTED
 ONLY WHERE THE UNITS ARE EQUIPPED WITH ELECTRIC COOKING
 EQUIPMENT. THIS IS NOT THE CASE FOR ALL UNITS. PROVIDE
 ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. NEC
 220.84
 9. PROVIDE ACCURATE LOAD CALCULATION AND PANEL SCHEDULE
 FOR PANEL GEDP. WHAT WILL THE LOAD ON THE GENERATOR BE?
 NEC 220
 10. PROVIDE DETAILS OF COMPLIANCE WITH THE EMERGENCY
 ENVIRONMENTAL CONTROL REQUIRED PER FLORIDA
 ADMINISTRATIVE CODE, RULE 58A-5.036
 11. SHEET E-7.2 STATES THE GENERATOR DESIGN IS BASED ON
 NEC 702, WHICH IS FOR OPTIONAL STANDBY SYSTEMS. THIS IS
 A LEGALLY REQUIRED SYSTEM. PROVIDE CLARIFICATION AND/OR
 CORRECTIONS. NEC 701.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  