Plan Review Notes
Plan Review Notes For Permit 20011223
Permit Number 20011223
Review Stop B
Sequence Number 1
Notes
Date Text
2020-07-20 14:01:02BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 20011223
 REVIEWED: AUGUST 17, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 FAIRHOUSING:
  
 1) REQUIREMENT 1 - SHOW AT LEAST ONE ACCESSIBLE ROUTE
 TO BUILDING ENTRANCE. WALKS THAT ARE PART OF ACCESSIBLE
 ROUTES BECOME RAMPS WHEN THEIR SLOPE EXCEEDS 5% (1 IN
 20). HANDRAILS ARE NOT REQUIRED ON WALKS WITH SLOPES
 BETWEEN 0% AND 5%, BUT THEY ARE REQUIRED ON THOSE
 STEEPER THAN 5% AND UP TO 8.33% (1 IN 12)
 - PROVIDE CIVIL PLANS TO VERIFY SLOPES THAT WILL OCCUR
 ON THE ACCESSIBLE PATH. PROVIDE SITE PLAN TO SHOW THE
 ACCESSIBLE PATH FROM PARKING OR OTHER PUBLIC ACCESS
 POINTS SUCH AS BUS STOP OR DROP OFF ZONE.
  
 2) REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON
 SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED
 TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT
 GRASPING OR TWISTING.
 - TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS
 TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE
 UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR
 SCHEDULE.
  
 3) REQUIREMENT 6 - REINFORCED WALLS FOR GRAB BARS
 - BARS ONLY NEED TO BE INSTALLED IN THE PUBLIC OR
 COMMON USE AREAS. ALL OF THE DWELLING UNITS ONLY NEED
 BLOCKING INSTALLED. SHEET A2.3 SHOWS THE BLOCKING AT
 TOILET AND WILL WORK. PLEASE ADD BLOCKING AT SHOWER
 BECAUSE I ONLY SEE CONTROL ZONE AND THAT WILL BE
 COVERED IN REQUIREMENT 7.
  
 4) REQUIREMENT 7 - USABLE KITCHENS.
 - I ONLY SEE ONE KITCHEN IN UNIT S101. PLEASE SHOW
 CLEAR FLOOR SPACE AT COOKTOP,REFRIDGERATOR AND SINK.
 THE CLEAR SPACE SHOULD BE CENTERED ON THE APPLIANCE.THE
 SINK DOESN'T APPEAR THAT IT WOULD WORK, SO THIS MAY
 NEED TO BE RE-WORKED. ALSO, CHECK
  
 5) REQUIREMENT 7 - COMMON LAUNDRY ROOMS.
 - SHOW CLEAR FLOOR SPACE AT WASHER AND DRYER IN LAUNDRY
 ROOM 118 AND LAUNDRY ROOMS ON FLOORS 2-4. THE CLEAR
 SPACE SHOULD BE CENTERED ON THE APPLIANCES.
  
  
 ACCESSIBILITY FBC 2017:
  
 6) 216.6 ENTRANCES. WHERE NOT ALL ENTRANCES COMPLY WITH
 404, ENTRANCES COMPLYING WITH 404 SHALL BE IDENTIFIED
 BY THE INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING
 WITH 703.7.2.1. DIRECTIONAL SIGNS COMPLYING WITH 703.5
 THAT INDICATE THE LOCATION OF THE NEAREST ENTRANCE
 COMPLYING WITH 404 SHALL BE PROVIDED AT ENTRANCES THAT
 DO NOT COMPLY WITH 404.
 ADVISORY 216.6 ENTRANCES.WHERE A DIRECTIONAL SIGN IS
 REQUIRED, IT SHOULD BE LOCATED TO MINIMIZE
 BACKTRACKING. IN SOME CASES, THIS COULDMEAN LOCATING A
 SIGN AT THE BEGINNING OF A ROUTE, NOT JUST AT THE
 INACCESSIBLE ENTRANCES TO A BUILDING.
 - ADD NOTE FOR SIGNAGE TO DIRECT TO LOCATION OF NEAREST
 ACCESSIBLE ENTRANCE. SIGNAGE TO MEET REQUIREMENMTS OF
 703.5
  
 7) 503 FBC(A)PASSENGER LOADING ZONES.
 - PLEASE SHOW MARKED AREA 5' X 20' AND SLOPES TO COMPLY
 WITH 503.4 FLOOR AND GROUND SURFACES. (A CIVIL DRAWING
 COULD BE PROVIDED TO SHOW SLOPES AND CURB CUT)
  
 8) 502.5 FBC[A] VERTICAL CLEARANCE. PARKING SPACES FOR
 VANS AND ACCESS AISLES AND VEHICULAR ROUTES SERVING
 THEM SHALL PROVIDE A VERTICAL CLEARANCE OF 98 INCHES
 MINIMUM.
 - VERIFY THAT GARAGE PROVIDES VAN CLEARANCE OF 98
 INCHES MINIMUM.
  
 9) 803.4 FBC[A] BENCHES. A BENCH COMPLYING WITH 903
 SHALL BE PROVIDED WITHIN THE ROOM.
  
 903.4 FBC[A] BACK SUPPORT. THE BENCH SHALL PROVIDE FOR
 BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. BACK
 SUPPORT SHALL BE 42 INCHES LONG MINIMUM AND SHALL
 EXTEND FROM A POINT 2 INCHES MAXIMUM ABOVE THE SEAT
 SURFACE TO A POINT 18 INCHES MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES MAXIMUM FROM
 THE REAR EDGE OF THE SEAT MEASURED HORIZONTALLY.
  
 OCCUPANCY:
  
 10) 107.5.3 FBC[AMENDED] GENERAL. SHEET LS-0.1
 - THE A-2 TAG AND FINE DINING TAGS ARE SHOWING POUND
 SIGNS INSTEAD OF THE SQ. FOOTAGE. PLEASE UPDATE SO THE
 SQ. FOOTAGE OF A-2 OCCUPANCY IS KNOWN.
  
 11) 303.3 FBC[B] GENERAL. SHEET LS-0.1
 - REVIEW GROUP A-2 THAT STATES DINING FACILITIES
 INCLUDING COMMERCIAL KITCHENS. SHOULD THE KITCHEN NOT
 BE CONSIDERED A-2 INSTEAD OF BUSINESS SINCE THE AREA
 SERVICED IS GREATER THAN 2500 SQ. FT.(SEE SECTION 304).
 HOWEVER, FOR EGRESS THEY YOU CAN USE OCCUPANT LOAD FOR
 COMMERCIAL KITCHEN THAT IS 200 GROSS PER TABLE 1004.1.2
  
 12) 107.5.3 FBC[AMENDED] GENERAL. SHEET LS-0.
 - OCCUPANY CLASSIFICATIONS ARE LISTED AS I-1, A-3, B,
 S-2 AND R-2, BUT WHEN I LOOK BELOW AT EXITING DATA I DO
 NOT SEE ALL THOSE OCCUPACIES LISTED. PLEASE UPDATE
 EXITING DATA TO MATCH ALL OCCUPANCY CLASSIFICATIONS.
  
 SITEWORK:
  
 13) 107.3.5.3 FBC[AMENDED] PROVIDE SEDIMENT CONTROL TO
 KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT
 PROPERTIES AND STORM DRAINS DURING CONSTRUCTION. YOU
 CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE
 PROTECTED TO THE DRAINAGE PLAN. SOME ENGINEERING
 STANDARD DETAILS CAN BE USED FROM WPB WEBSITE-POLLUTION
 CONTROL. HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUB
 LIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 14) 107.3.5.3 FBC[AMENDED] PAVING AND DRAINAGE PLANS
 - PROVIDE CIVIL PLANS TO SHOW SLOPES, ELEVATIONS AND
 DRAINAGE AS IT RELATES TO PEDESTRIAN PATHWAYS AND
 ACCESS(FULL SET NOT REQUIRED)
  
 15) 107.5.3 FBC[AMENDED] SEPARATE PERMIT REQUIRED FOR
 VIBRO COMPACTION.
 - GEOTECHNICAL REPORT (RECEIVED, VIBRO-COMPACTION PROBE
 LAYOUT, FOUNDATION PLAN, AND STORM WATER POLLUTION
 PREVENTION PLAN (REQUESTED)
  
 16) 406.5.2 FBC(B)OPENINGS IN INTERIOR WALLS FOR OPEN
 PARKING.
 - PLEASE ADD OPENING PERCENTAGES FOR INTERIOR.WALLS OF
 OPEN GARAGE. SHEET LS-0.2 DOESN'T APPEAR TO HAVE
 OPENINGS ON INTERIOR WALL.
  
 17) 1609.4.3 FBC[B] EXPOSURE CATEGORIES. AN EXPOSURE
 CATEGORY SHALL BE DETERMINED IN ACCORDANCE WITH THE
 FOLLOWING: EXPOSURE B. FOR BUILDINGS WITH A MEAN ROOF
 HEIGHT OF LESS THAN OR EQUAL TO 30 FEET, EXPOSURE B
 SHALL APPLY WHERE THE GROUND SURFACE ROUGHNESS, AS
 DEFINED BY SURFACE ROUGHNESS B, PREVAILS IN THE UPWIND
 DIRECTION FOR A DISTANCE OF AT LEAST 1,500 FEET. FOR
 BUILDINGS WITH A MEAN ROOF HEIGHT GREATER THAN 30 FEET,
 EXPOSURE B SHALL APPLY WHERE SURFACE ROUGHNESS B
 PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT
 LEAST 2,600 FEET OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER.
 EXPOSURE C. EXPOSURE C SHALL APPLY FOR ALL CASES WHERE
 EXPOSURE B OR D DOES NOT APPLY.
 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND
 SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D,
 PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT
 LEAST 5,000 FEET OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL ALSO
 APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY
 UPWIND OF THE SITE IS B OR C, AND THE SITE IS WITHIN A
 DISTANCE OF 600 FEET OR 20 TIMES THE BUILDING HEIGHT,
 WHICHEVER IS GREATER, FROM AN EXPOSURE D CONDITION AS
 DEFINED IN THE PREVIOUS SENTENCE.
 - IN REVIEWING LOCATION I WOULD PUT THIS LOCATION AT A
 CATEGORY C INSTEAD OF D. PLEASE REVIEW THIS WITH NEXT
 COMMENT ABOUT CATEGORY SELECTION AND PLEASE ADJUST IF
 APPLICABLE. PLEASE CONSIDER EXPOSURE C WITH CATEGORY
 III DESIGNATION OR PROVIDE JUSTIFICATION FOR THE
 CURRENT CATEGORY II SELCTION WITH D EXPOSURE.
  
 18) 1604.5 FBC[B] RISK CATEGORY. EACH BUILDING AND
 STRUCTURE SHALL BE ASSIGNED A RISK CATEGORY IN
 ACCORDANCE WITH TABLE 1604.5. WHERE A REFERENCED
 STANDARD SPECIFIES AN OCCUPANCY CATEGORY, THE RISK
 CATEGORY SHALL NOT BE TAKEN AS LOWER THAN THE OCCUPANCY
 CATEGORY SPECIFIED THEREIN. WHERE A REFERENCED STANDARD
 SPECIFIES THAT THE ASSIGNMENT OF A RISK CATEGORY BE IN
 ACCORDANCE WITH ASCE 7, TABLE 1.5-1, TABLE 1604.5 SHALL
 BE USED IN LIEU OF ASCE 7, TABLE 1.5-1. 1604.5.1
 MULTIPLE OCCUPANCIES.
 - TABLE 1604.5 FBC[B]. PLEASE REVIEW CRITERIA FOR
 CATEGORY II BEING SELECTED. CATEGORY III IS USED FOR
 BUILDINGS THAT REPRESENT A SUBSTAINTIAL HAZARD TO HUMAN
 LIFE. THIS BUILDING HAS HIGH OCCUPANT LOAD, OCCUPANTS
 UNDER CUSTODIAL CARE AND OCCUPANTS UNDER MEMORY CARE.
  
 19)3202.2 FBC[B]ENCROACHMENTS ABOVE GRADE AND BELOW 8
 FEET IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC
 RIGHT-OF-WAY ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN
 HEIGHT SHALL BE PROHIBITED EXCEPT AS PROVIDED FOR IN
 SECTIONS 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS
 SHALL NOT OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
 - CHECK DOOR FROM STAIR 3 APPEARS TO CROSS PROPERTY
 LINES.
  
 20) 3002.4 FBC[B] ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER. ANY BUILDING THAT IS MORE THAN THREE STORIES
 HIGH OR IN WHICH THE VERTICAL DISTANCE BETWEEN THE
 BOTTOM TERMINAL LANDING AND THE TOP TERMINAL LANDING
 EXCEEDS 25 FEET (7620 MM), MUST BE CONSTRUCTED TO
 CONTAIN AT LEAST ONE PASSENGER ELEVATOR THAT IS
 OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL
 BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE AN
 AMBULANCE STRETCHER 24 INCHES BY 76 INCHES (610 MM BY
 1950 MM) WITH NOT LESS THAN 5-INCH (127 MM) RADIUS
 CORNERS, IN THE HORIZONTAL, OPEN POSITION AND SHALL BE
 IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY
 MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL BE
 NOT LESS THAN 3 INCHES (76 MM) IN HEIGHT AND SHALL BE
 PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME.
 - INDICATE WHICH PASSENGER ELEVATOR WILL BE IDENTIFIED
 TO ACCOMMODATE STRETCHER.
  
 ASSEMBLIES:
  
 21) PLEASE PROVIDE OR STATE WHERE TO FIND TESTED
 ASSEMBLIES FOR FIRE RATED SPECIFIED IN TABLE 601 FOR
 FLOORS AND OTHER RATED ASSEMBLIES AS REQUIRED FROM
 TABLE 601.
  
 SUBMITTALS:
  
 22) 1014 FBC [B] GUARDS AND HANDRAILS. 1607.8 FBC [B]
 LOADS ON HANDRAILS AND GUARDRAILS. PROVIDE HANDRAIL AND
 GUARDRAIL ENGINEERING, OR INDICATE THAT YOU WOULD LIKE
 IT DEFERRED.
  
 107.3.4.1 FBC[AMENDED] DEFERRAL OF ANY SUBMITTAL ITEMS
 SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR
 REVIEW, AND THEN FORWARED TO THE BUILDING OFFICIAL
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE
 INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 107.3.4.1 FBC[AMENDED] IF ANY SPEC SHEETS OR PRODUCT
 APPROVALS ARE ADDED, PLEASE UPLOAD THEM AS MULTIPAGE
 FORMAT PDF IN SUPPORTING DOCUMENTS.
  
 23) 806.3 FBC[B] COMBUSTIBLE DECORATIVE MATERIALS. IN
 OTHER THAN GROUP I-3, CURTAINS, DRAPERIES, FABRIC
 HANGINGS AND SIMILAR COMBUSTIBLE DECORATIVE MATERIALS
 SUSPENDED FROM WALLS OR CEILINGS SHALL COMPLY WITH
 SECTION 806.4 AND SHALL NOT EXCEED 10 PERCENT OF THE
 SPECIFIC WALL OR CEILING AREA TO WHICH SUCH MATERIALS
 ARE ATTACHED. FIXED OR MOVABLE WALLS AND PARTITIONS,
 PANELING, WALL PADS AND CRASH PADS APPLIED STRUCTURALLY
 OR FOR DECORATION, ACOUSTICAL CORRECTION, SURFACE
 INSULATION OR OTHER PURPOSES SHALL BE CONSIDERED
 INTERIOR FINISH SHALL COMPLY WITH SECTION 803 AND SHALL
 NOT BE CONSIDERED DECORATIVE MATERIALS OR FURNISHINGS.
 - (SEE 806.3 FOR EXCEPTIONS)
  
 806.4 FBC[B] ACCEPTANCE CRITERIA AND REPORTS. WHERE
 REQUIRED TO EXHIBIT IMPROVED FIRE PERFORMANCE,
 CURTAINS, DRAPERIES, FABRIC HANGINGS AND SIMILAR
 COMBUSTIBLE DECORATIVE MATERIALS SUSPENDED FROM WALLS
 OR CEILINGS SHALL BE TESTED BY AN APPROVED AGENCY AND
 MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF TEST
 1 OR 2, AS APPROPRIATE, OF NFPA 701, OR EXHIBIT A
 MAXIMUM HEAT RELEASE RATE OF 100 KW WHEN TESTED IN
 ACCORDANCE WITH NFPA 289, USING THE 20 KW IGNITION
 SOURCE. REPORTS OF TEST RESULTS SHALL BE PREPARED IN
 ACCORDANCE WITH THE TEST METHOD USED AND FURNISHED TO
 THE BUILDING OFFICIAL UPON REQUEST.
  -PROVIDE AS SUBMITTAL TO DEVELOPMENT SERVICES OFFICE
  
 24) 1207.2 FBC[B] FLOORING SUBMITTAL.
 - TYPE OF CEILING ASSEMBLY INCLUDING THICKNESS OF
 CONCRETE AND IF THERE IS A SOUND RATED ASSEMBLY IN UNIT
 BELOW.
  
 1207.2 FBC[B] PLEASE ADVISE ,VIA EMAIL, WHAT FLOORING
 AND UNDERLAYMENT ARE PROPOSED? IF THE UNDERLAYMENT
 PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST
 REPORTS ON FILE, THE FOLLOWING REPORTS WILL BE
 REQUIRED:
 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND FLOOR
 COVERING MATERIALS SHALL COMPLY WITH SECTIONS 804.2
 THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND
 COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL,
 LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING
 MATERIALS THAT ARE NOT COMPRISED OF FIBERS.
  
 TEMPORARY CONSTRUCTION:
  
 25) 3104.1.1 FBC[B] APPLICATION. PEDESTRIAN WALKWAYS
 SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH
 SECTIONS 3104.2 THROUGH 3104.9. TUNNELS SHALL BE
 DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH SECTIONS
 3104.2 AND 3104.10.
 - SEPARATE PERMIT NEEDED TEMP FENCING AND RIGHT OF WAY
 PERMIT FOR SIDEWALK CLOSURES.
  
 26) 3306.1 FBC[B] PROTECTION REQUIRED. PEDESTRIANS
 SHALL BE PROTECTED DURING CONSTRUCTION, REMODELING AND
 DEMOLITION ACTIVITIES AS REQUIRED BY THIS CHAPTER AND
 TABLE 3306.1. SIGNS SHALL BE PROVIDED TO DIRECT
 PEDESTRIAN TRAFFIC. 3306.2 FBC[B] WALKWAYS. A WALKWAY
 SHALL BE PROVIDED FOR PEDESTRIAN TRAVEL IN FRONT OF
 EVERY CONSTRUCTION AND DEMOLITION SITE UNLESS THE
 APPLICABLE GOVERNING AUTHORITY AUTHORIZES THE SIDEWALK
 TO BE FENCED OR CLOSED. WALKWAYS SHALL BE OF SUFFICIENT
 WIDTH TO ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO
 CASE SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH.
 WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING
 SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE
 WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL
 IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD
 BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF)
  
 27) 3306.7 FBC[B] COVERED WALKWAYS. COVERED WALKWAYS
 SHALL HAVE A CLEAR HEIGHT OF NOT LESS THAN 8 FEET (2438
 MM) AS MEASURED FROM THE FLOOR SURFACE TO THE CANOPY
 OVERHEAD. ADEQUATE LIGHTING SHALL BE PROVIDED AT ALL
 TIMES. COVERED WALKWAYS SHALL BE DESIGNED TO SUPPORT
 ALL IMPOSED LOADS. IN NO CASE SHALL THE DESIGN LIVE
 LOAD BE LESS THAN 150 PSF (7.2 KN/M2) FOR THE ENTIRE
 STRUCTURE.
  
 PROVISOS:
  
 A) AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED
 PRIOR TO C.O.
 B) DEFERRED SUBMITTALS - COMPONENT & CLADDING PRODUCT
 APPROVALS SUBMITTED TO PLAN REVIEW OFFICE. PRODUCT
 APPROVALS FOR LOUVERS AND EQUIPMENT STANDS.
 C) VEHICLE BARRIER SUBMITTAL TO PLAN REVIEW OFFICE
 D) ROOF ENGINEERING AND PRODUCT APPOVAL TO BE SUBMITTED
 WITH ROOF SUB-PERMIT APPLICATION. SEE ENERGY
 CALCULATIONS THAT CALL FOR HIGH ALBEDO ROOF.
 E) SEPARATE PERMITS REQUIRED FOR - GENERATOR, LIGHT
 POLES/SITE LIGHTING, FIRE ALARM, FIRE SPRINKLER, LOW
 VOLTAGE, ACCESS, LANDSCAPING, IRRIGATION, POOL,
 TEMPORARY FENCE AND RIGHT OF WAY PERMITS(ENGINEERING)
 F) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
 - NO RESPONSE REQUIRED. THESE WILL BE ADDED TO THE
 PLANS AT FINAL STAMPING.
  
 NOTES:
  
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F 8-5) TO
 DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected]
  
  
  