2020-02-06 16:31:18 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PROVIDE THE WIND DESIGN DATA ON THE PLANS. FBC | | 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS SHALL | | BE DESIGNED TO RESIST THE LOADS SET FORTH IN CHAPTER 16 | | OF THIS CODE EXCEPT THAT STRUCTURES OR PARTS THEREOF | | WHICH ARE INTENDED TO BE REMOVED OR REPOSITIONED DURING | | PERIODS OF HIGH WIND VELOCITY SHALL BE DESIGNED IN | | THEIR OPEN OR EXTENDED POSITION TO DESIGN PRESSURES | | BASED ON A BASIC WIND SPEED OF MINIMUM 115 MPH, | | 3-SECOND WIND GUST WITH APPLICABLE SHAPE FACTORS TO | | RESIST NOT LESS THAN 10 PSF ROOF LIVE LOAD. | | | | |
|