2020-02-06 16:31:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE THE WIND DESIGN DATA ON THE PLANS. FBC
 3105.5.1 LOADS. RIGID AWNINGS AND CANOPY SHUTTERS SHALL
 BE DESIGNED TO RESIST THE LOADS SET FORTH IN CHAPTER 16
 OF THIS CODE EXCEPT THAT STRUCTURES OR PARTS THEREOF
 WHICH ARE INTENDED TO BE REMOVED OR REPOSITIONED DURING
 PERIODS OF HIGH WIND VELOCITY SHALL BE DESIGNED IN
 THEIR OPEN OR EXTENDED POSITION TO DESIGN PRESSURES
 BASED ON A BASIC WIND SPEED OF MINIMUM 115 MPH,
 3-SECOND WIND GUST WITH APPLICABLE SHAPE FACTORS TO
 RESIST NOT LESS THAN 10 PSF ROOF LIVE LOAD.
  
  