2020-02-03 09:36:48 | RESIDENTIAL (R2) ROOF TILE SUBMITTAL BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- CLEARLY SPECIFY THE SPECIFIC ROOF TILE FASTENING AS |
| REQUIRED BY SEC. 107.2.1.1 CITY AMENDMENTS. |
| ROOF TILE NOA 19-0814.01 SUBMITTED INDICATE ON PAGE 5 |
| OF 9 THAT "YOU CAN USE ANY OF THE FASTENER TYPE WITH |
| EXCEPTION OF 1-10D OR SCREW SHANK NAIL". THIS GENERAL |
| SPECIFICATION IS NOT ACCEPTABLE BECAUSE MOST OF THE |
| FASTENER SPECIFICATIONS SHOWN ON THIS PAGE DON'T |
| MEET THE ATTACHMENT RESISTANCE BASED ON THE HEIGHT AND |
| BUILDING EXPOSURE OF THIS BUILDING. DESIGNER OF RECORD |
| TO SPECIFY FASTENER TYPE THAT WILL MEET THE REQUIRED |
| ATTACHMENT RESISTANCE. |
| |
| 2- A) IF USING ROOF TILE ADHESIVE, THEN PROVIDE PRODUCT |
| APPROVAL FOR ROOF TILE ADHESIVE LISTED ON THE ROOF TILE |
| NOA. FAC 61G20.3001. |
| |
| B) CLEARLY MARK ADHESIVE PADDY SIZE ON THE ROOF TILE |
| NOA AND ROOF TILE ADHESIVE NOA AS REQUIRED BY CITY |
| POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE |
| WITH THE DESIGN PRESSURES OF SEC R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |