2020-02-03 09:36:48RESIDENTIAL (R2) ROOF TILE SUBMITTAL BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- CLEARLY SPECIFY THE SPECIFIC ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.1 CITY AMENDMENTS.
 ROOF TILE NOA 19-0814.01 SUBMITTED INDICATE ON PAGE 5
 OF 9 THAT "YOU CAN USE ANY OF THE FASTENER TYPE WITH
 EXCEPTION OF 1-10D OR SCREW SHANK NAIL". THIS GENERAL
 SPECIFICATION IS NOT ACCEPTABLE BECAUSE MOST OF THE
 FASTENER SPECIFICATIONS SHOWN ON THIS PAGE DON'T
 MEET THE ATTACHMENT RESISTANCE BASED ON THE HEIGHT AND
 BUILDING EXPOSURE OF THIS BUILDING. DESIGNER OF RECORD
 TO SPECIFY FASTENER TYPE THAT WILL MEET THE REQUIRED
 ATTACHMENT RESISTANCE.
  
 2- A) IF USING ROOF TILE ADHESIVE, THEN PROVIDE PRODUCT
 APPROVAL FOR ROOF TILE ADHESIVE LISTED ON THE ROOF TILE
 NOA. FAC 61G20.3001.
  
 B) CLEARLY MARK ADHESIVE PADDY SIZE ON THE ROOF TILE
 NOA AND ROOF TILE ADHESIVE NOA AS REQUIRED BY CITY
 POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC R301.2.1
 FBC-RESIDENTIAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION