Plan Review Notes For Permit 20011193 |
Permit Number |
20011193 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-02-06 11:16:35 | FLOORING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - | | 1) THE BUILDING AT 1617 N FLAGLER HAS A 6" SLAB - I | | NEED AN "ACOUSTICAL LABORATORY TEST REPORT" THAT SHOWS | | THE TEST DESCRIPTION FOR A 6" THICK SLAB ( NO CEILING | | ). CONTACT THE UNDERLAYMENT MANUFACTURE OR THE STORE | | THAT YOU ARE GETTING THE UNDERLAYMENT (PROFLEX) FROMAND | | ASK FOR THE "ACOUSTICAL LABORATORY TEST REPORT". NEED | | AN IIC (ASTM E989-06) AND AN STC (ASTM E90) OF 50 OR | | HIGHER. IF PROFLEX DOESN'T HAVE THE TEST REPORT PLEASE | | TRY ANOTHER PRODUCT - - SEE FBC 1207 | | |
|