2020-02-18 10:13:47 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SEPARATE PERMIT IS REQUIRED FOR BACKFLOW ASSEMBLIES |
| PER WPB UTILITIES. PLACE NOTE ON PLAN |
| |
| 2. ALL PLUMBING WORK SHALL COMPLY WITH FBC PLUMBING 6TH |
| EDITION 2017 PLEASE CORRECT NOTE #7 ON SHEET P101 UNDER |
| GENERAL NOTES. |
| |
| 3. PROVIDE PIPING DETAIL WATER AND SANITARY FOR THE |
| WATER FOUNTAIN SHOWING ALL SHUT VALVE P-TRAP AND VENT. |
| PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| |
| 4. PROVIDE DETAIL FOR ELECTRICAL OUTLET PEDESTAL WITH |
| HOSE BIB NOTE ON PLAN REFERENCE ELECTRICAL DRAWING I |
| COULD NOT LOCATE ANY DETAILS. PER WPB AMEND TO FBC |
| 107.3.5.1.3(13) |
| |
| 5. EACH HOSE BIB IS REQUIRED TO HAVE A VACUUM BREAKER |
| AND SHUT OFF VALVE. PER FBC PL 608.15.4.2, 606.2(2) |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |