Plan Review Notes
Plan Review Notes For Permit 20011157
Permit Number 20011157
Review Stop P
Sequence Number 1
Notes
Date Text
2020-02-18 10:13:471ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SEPARATE PERMIT IS REQUIRED FOR BACKFLOW ASSEMBLIES
 PER WPB UTILITIES. PLACE NOTE ON PLAN
  
 2. ALL PLUMBING WORK SHALL COMPLY WITH FBC PLUMBING 6TH
 EDITION 2017 PLEASE CORRECT NOTE #7 ON SHEET P101 UNDER
 GENERAL NOTES.
  
 3. PROVIDE PIPING DETAIL WATER AND SANITARY FOR THE
 WATER FOUNTAIN SHOWING ALL SHUT VALVE P-TRAP AND VENT.
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 4. PROVIDE DETAIL FOR ELECTRICAL OUTLET PEDESTAL WITH
 HOSE BIB NOTE ON PLAN REFERENCE ELECTRICAL DRAWING I
 COULD NOT LOCATE ANY DETAILS. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 5. EACH HOSE BIB IS REQUIRED TO HAVE A VACUUM BREAKER
 AND SHUT OFF VALVE. PER FBC PL 608.15.4.2, 606.2(2)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  