Plan Review Notes
Plan Review Notes For Permit 20011157
Permit Number 20011157
Review Stop B
Sequence Number 1
Notes
Date Text
2020-02-13 16:46:50HEART AND SOUL PARK
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE SIGNED AND SEALED GATEWAY WALL
 DETAILS FROM AN ARCHITECT OR ENGINEER TO COMPLY WITH
 FBC 1609
 2) PLEASE PROVIDE SIGNED AND SEALED PLAYGROUND
 EQUIPMENT FOUNDATION AND ATTACHMENTS TO THE FOUNDATION
 FBC 1609
 3) PLEASE PROVIDE SIGNED AND SEALED DETAILS FOR THE
 SHADE SAIL - (FOUNDATION, POLE DESIGNATION, HEIGHT FROM
 GROUND, AND ALL ATTACHMENTS). FBC 1609 AND 3102
 4) PLEASE PROVIDE SIGNED AND SEALED FOUNDATION, POLE
 AND ATTACHMENT DETAILS FOR THE LIGHT POLES TO COMPLY
 WITH FBC 1609
 5) PLEASE SHOW THE WIND DESIGN CRITERIA USED FOR THE
 STRUCTURES LISTED ABOVE PER FBC 1603.1.4
 6) ALL PROVIDED SHOP DRAWINGS/DETAILS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE PARK DESIGNER OF
 RECORD. FBC WPB AMENDMENTS 107.3.4
 7) PLEASE PROVIDE AN ORIGINAL SIGNED AND SEALED COPY OF
 THE GEOTECHNICAL REPORT (AN ELECTRONICALLY SIGNED
 DOCUMENT WOULD BE BETTER FOR ELECTRONIC PERMITTING).
  