2020-01-28 13:58:50 | ****CORRECTIONS**** |
| |
| ROGER MCPHERSON |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1) BUILDING PERMIT APPLICATION SHOWS 1 DOOR REPLACEMENT |
| - PROVIDED COPY OF THE CONTRACT SHOWS NEW DOOR OPENING. |
| (PLEASE CLARIFY ON THE APPLICATION). FBC 107.2 |
| 2) PLEASE PROVIDE STRUCTURAL DETAILS FOR THE DOOR |
| OPENING. FBC R301.2.1 |
| 3) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF |
| THE NEW DOORS. FBC R 107.3.5.3 |
| 4) PLEASE PROVIDE THE COMPLETE FLORIDA PRODUCT APPROVAL |
| ( FRONT PAGES ARE MISSING). FBC R301.2.1.2 |
| 5) PRODUCT APPROVAL SUPPLIED DOES NOT MEET IMPACT |
| REQUIREMENTS - PLEASE PROVIDE A PRODUCT APPROVAL FOR |
| THE REQUIRED SHUTTERS. FBC R 301.2.1.2 |
| 6) CONTRACTORS SIGNATURE ON THE PROVIDED PERMIT |
| APPLICATION NEEDS TO BE NOTARIZED AS VALUE APPEARS TO |
| BE MORE THAN $2500.00 FBC 107 |
| 7) PLEASE SHOW JOB COST BREAK DOWN PER FBC 109.3 |
| 8) 1. FBC R 301, COMPLETE THE "SCHEDULE FOR |
| INSTALLATION OF OPENING PROTECTIVE DEVICES" OR PROVIDE |
| ALL INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS |
| EXCEL SPREADSHEET): |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS?PAGE=2 |