2020-02-11 14:16:49 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20011048 |
| ADD: 1801 N FLAGLER DR. SUITE # 826 |
| CONT: REGIONS PROPERTY MGMT. & CONSTRUCTION |
| TEL: 561-292-9881 |
| E-MAIL: RGOING@ REGIONSRC.COM |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. FEB. 11/2020 |
| ACTION: DENIED |
| |
| NOTICE 08/05/2019 4 X FEE BLDG, ELEC, PLBG- INTERIOR |
| ALTERATIONS BATH &FLOORING. |
| |
| 1) THE DOLLAR AMOUNT OF $1,500.00 IS EXTREMELY, |
| EXTREMELY LOW!!!!!!! IF THE CONTRACTOR DOES NOT PROVIDE |
| AN ACCURATE VALUE FOR THE REMODEL OF THE BATHROOM IN A |
| HIGHRISE, THEN THE PLANS EXAMINER WILL ASSESS A VALUE |
| FOR MARSHALL-SWIFT, OR THE INTERNATIONAL CODE CONGRESS |
| TABLE WITH REGIONAL ADJUSTMENTS. |
| |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER OF THE ADMINISTRATIVE CODE SECTION 108.3 |
| BUILDING PERMIT VALUATION. IF, IN THE OPINION OF THE |
| BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR |
| PLUMBING SYSTEMS APPEARS TO BE UNDER ESTIMATED ON THE |
| APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE |
| THE EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| ONE SHEET. |
| |
| 3) THE PLAN SUBMITTED IS DEFICIENT IN SHOWING THE SCOPE |
| OF WORK FOR THE VARIOUS TRADES, BUILDING, ELECTRIC & |
| PLUMBING AND THE CHANGES MADE TO THE BATHROOM. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. |
| |
| IN THE SUBMITTED PLAN 2 OF THE WALLS BACK WALL IS A |
| FIRE RATED WALL AS WELL AS THE TENANT SEPARATION WALL. |
| THE PLAN DOES NOT PROVIDE THE TYPE OF MATERIAL USED FOR |
| THE FIRE RATING OF THESE WALLS. PLEASE SHOW HOW |
| COMPLIANCE WITH THE 2017 FBC-B SECTION 420.2 SEPARATION |
| WALLS IS TO BE ACHIEVED. CONSTRUCTION OF FIRE |
| PARTITIONS SHALL BE BUILT IN ACCORDANCE WITH SECTION |
| 708.3 FIRE RESISTANCE RATING, AND 708.4 CONTINUITY. |
| |
| 4) THESE SAME WALLS WILL ALSO NEED TO SHOW HOW |
| COMPLIANCE WITH AIR-BORNE SOUND ( WALL INSULATION) WILL |
| BE ACHIEVED. SEE THE 2017 FBC-B 1207.2 FOR AIR BORNE |
| SOUND. |
| |
| 5) THE WALLS OF THE NEW SHOWER SURROUND WILL ALSO NEED |
| TO MEET THE REQUIREMENTS FOR BASE FOR TILE AND OR |
| MARBLE. SEE THE 2017 FBC-B 2509.2 SEE 2509.3 FOR |
| LIMITATIONS, WATER-RESISTANT GYPSUM BACKING SHALL NOT |
| BE USED IN THE FOLLOWING LOCATIONS: |
| 1) OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| COMPARTMENTS. |
| 2) WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| |
| 6) BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2017) FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING |
| ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED |
| FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET |
| THE QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS |
| FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED |
| CEILING: |
| PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES) |
| SHOWING COMPLIANCE WITH ALL 3 REQUIREMENTS: |
| |
| 6A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET |
| |
| 6 B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 6C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |