2020-02-13 08:47:23 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #20011032 |
| 2/13/20 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE AC PLAN IS INCOMPLETE. |
| |
| A) PROVIDE RETURN AIR FROM THE BEDROOMS- SECTION |
| M1602.3 FBC RES. |
| |
| B) SHOW THE SUPPLY CFMS AT EACH DIFFUSER LOCATION- |
| M1601.1 FBC RES. |
| |
| C) VERIFY 10' CLEARANCE FROM THE COOKING APPLIANCES TO |
| THE MAIN RETURN IN THE KITCHEN- M1602.2 FBC RES |
| |
| D) NO ACCESS TO AIR HANDLER IN ATTIC SHOWN- M1305.1.3 |
| FBC RES |
| |
| D) LOCATION OF CONDENSER AND INSTALLATION DETAIL NOT |
| PROVIDED- M1305.1.4.1 & M1401.4 FBC RES. |
| |
| 2) NO ELECTRICAL PLAN SUBMITTED TO INDICATE CIRCUITRY, |
| WIRE AND BREAKER SIZES- SECTION 107.2.1 WPB. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE |
| RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. |
| THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |