Plan Review Notes
Plan Review Notes For Permit 20011032
Permit Number 20011032
Review Stop M
Sequence Number 2
Notes
Date Text
2020-02-13 08:47:232ND REVIEW FBC-2017 MECHANICAL
 PERMIT #20011032
 2/13/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC PLAN IS INCOMPLETE.
  
 A) PROVIDE RETURN AIR FROM THE BEDROOMS- SECTION
 M1602.3 FBC RES.
  
 B) SHOW THE SUPPLY CFMS AT EACH DIFFUSER LOCATION-
 M1601.1 FBC RES.
  
 C) VERIFY 10' CLEARANCE FROM THE COOKING APPLIANCES TO
 THE MAIN RETURN IN THE KITCHEN- M1602.2 FBC RES
  
 D) NO ACCESS TO AIR HANDLER IN ATTIC SHOWN- M1305.1.3
 FBC RES
  
 D) LOCATION OF CONDENSER AND INSTALLATION DETAIL NOT
 PROVIDED- M1305.1.4.1 & M1401.4 FBC RES.
  
 2) NO ELECTRICAL PLAN SUBMITTED TO INDICATE CIRCUITRY,
 WIRE AND BREAKER SIZES- SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  