Date Text
2020-04-23 13:21:23 
 NOTE: PLAN SHEETS A1.2.1 AND A1.3.1 WHICH WERE
 REFERENCED IN THE RESPONSE LETTER DATED 4/2/2020, DO
 NOT PERTAIN TO PERMIT 20010978 WHICH IS FOR WORK TO BE
 DONE ON THE SECOND FLOOR.
 1) PER WPB FBC 107.2.1, PROVIDE LOCATION OF THE
 REQUIRED BI-LEVEL DRINKING FOUNTAIN CALLED OUT IN
 PLUMBING FIXTURE SCHEDULE NOTED ON PLAN SHEET P0.1.
 ARCHITECT TO PROVIDE ADEQUATE SPACE FOR SAID DRINKING
 FOUNTAIN, WHICH SHALL BE CLEARLY SHOWN AS THE REQUIRED
 BI-LEVEL DRINKING FOUNTAIN ON ARCHITECTURAL PLAN SHEETS
 PERTAINING TO THE SECOND FLOOR RENOVATION FOR WHICH IS
 APPLICABLE TO PERMIT 20010978, THAT WILL COMPLY WITH
 THE REQUIREMENTS OF FBC ACC CHAPTERS 3 AND 6.
 ADDITIONALLY, THE DRINKING FOUNTAIN, WHICH SHALL BE
 CLEARLY SHOWN AS THE REQUIRED BI-LEVEL DRINKING
 FOUNTAIN ON PLAN SHEET P2.1. 2ND REQUEST.
 2) PER WPB FBC 107.2.1, ARCHITECT TO PROVIDE ON
 ARCHITECTURAL PLAN SHEETS PERTAINING TO THE SECOND
 FLOOR RENOVATION FOR WHICH IS APPLICABLE TO PERMIT
 20010978, CLEAR FLOOR SPACES, REACH RANGES, AND TURNING
 SPACES AS REQUIRED FOR SINK, ICE MAKERS, FRIDGE/
 FREEZER, DRINKING FOUNTAIN. FBC-ACC 306, 306, 804.
 3) PER WPB FBC 107.2.1, ARCHITECT TO PROVIDE A DETAIL
 FOR THE DRINKING FOUNTAIN ON ARCHITECTURAL PLAN SHEETS
 PERTAINING TO THE SECOND FLOOR RENOVATION FOR WHICH IS
 APPLICABLE TO PERMIT 20010978, SHOWING COMPLIANCE WITH
 FBC ACC 307 AND 602.
 4) RE: P0.1; THE FIXTURE PLUMBING SCHEDULE APPEARS TO
 APPLY TO OTHER RENOVATIONS IN ADDITION TO THE SECOND
 FLOOR RENOVATION. PER FBC 107.2.1, INDICATE ON THE
 PLUMBING FIXTURE SCHEDULE THAT S-1 AND NOT S-2 IS
 APPLICABLE TO THE SECOND FLOOR RENOVATION.
 6) RE: P0.1; TYPICAL PLUMBING FIXTURE CONNECTION
 SCHEDULE. PLEASE COMPLY WITH THE FOLLOWING:
 A. COFFEE MAKER; PROVIDE BACKFLOW PREVENTOR FOR WATER
 CONNECTION
 B. FILTER; PROVIDE MANUFACTURER'S SPECIFICATION AND
 INSTALLATION MANUAL.
 1. IF RO SYSTEM IS PROVIDED THEN A BACKFLOW PREVENTOR
 SHALL BE REQUIRED FOR THE WATER CONNECTION AND A
 TRAPPED AND VENTED ACCESSIBLE OPEN RECEPTACLE SHALL BE
 REQUIRED FOR THE DRAIN WHICH SHALL DISCHARGE TO THE
 OPEN RECEPTACLE THROUGH AN AIR GAP. THIS INFORMATION
 SHALL BE SHOWN IN PIPING ARRANGEMENT.
 2. IF A REMOVABLE/REPLACEMENT TYPE FILTER IS PROVIDED,
 A BACKFLOW PREVENTER SHALL BE REQUIRED FOR THE WATER
 CONNECTION.
 C. REFRIGERATOR; PROVIDE BACKFLOW PREVENTOR FOR WATER
 CONNECTION
 7) PER WPB FBC 107.2.1, PROVIDE WATER AND SANITARY
 RISER DIAGRAMS FOR THE PLUMBING WORK SHOWN IN PLAN
 VIEW. PLEASE NOTE THAT AN AAV SHALL NOT BE PERMITTED AS
 A FIXTURE VENT PER FBC PL 918.3.1 UNLESS THE HORIZONTAL
 BRANCH IS PROVIDED WITH A RELIEF VENT THAT CONNECTS TO
 THE VENT STACK.
 8) IF DRINKING FOUNTAIN IS TO BE RELOCATED IN ORDER TO
 COMPLY WITH THE REQUIREMENTS OF FBC ACC 307 AND 602,
 THEN PER WPB FBC 107.2.1, PROVIDE PLAN VIEW AND RISER
 DIAGRAMS FOR THE REQUIRED PIPING.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW