2020-04-23 13:21:23 | |
| NOTE: PLAN SHEETS A1.2.1 AND A1.3.1 WHICH WERE |
| REFERENCED IN THE RESPONSE LETTER DATED 4/2/2020, DO |
| NOT PERTAIN TO PERMIT 20010978 WHICH IS FOR WORK TO BE |
| DONE ON THE SECOND FLOOR. |
| 1) PER WPB FBC 107.2.1, PROVIDE LOCATION OF THE |
| REQUIRED BI-LEVEL DRINKING FOUNTAIN CALLED OUT IN |
| PLUMBING FIXTURE SCHEDULE NOTED ON PLAN SHEET P0.1. |
| ARCHITECT TO PROVIDE ADEQUATE SPACE FOR SAID DRINKING |
| FOUNTAIN, WHICH SHALL BE CLEARLY SHOWN AS THE REQUIRED |
| BI-LEVEL DRINKING FOUNTAIN ON ARCHITECTURAL PLAN SHEETS |
| PERTAINING TO THE SECOND FLOOR RENOVATION FOR WHICH IS |
| APPLICABLE TO PERMIT 20010978, THAT WILL COMPLY WITH |
| THE REQUIREMENTS OF FBC ACC CHAPTERS 3 AND 6. |
| ADDITIONALLY, THE DRINKING FOUNTAIN, WHICH SHALL BE |
| CLEARLY SHOWN AS THE REQUIRED BI-LEVEL DRINKING |
| FOUNTAIN ON PLAN SHEET P2.1. 2ND REQUEST. |
| 2) PER WPB FBC 107.2.1, ARCHITECT TO PROVIDE ON |
| ARCHITECTURAL PLAN SHEETS PERTAINING TO THE SECOND |
| FLOOR RENOVATION FOR WHICH IS APPLICABLE TO PERMIT |
| 20010978, CLEAR FLOOR SPACES, REACH RANGES, AND TURNING |
| SPACES AS REQUIRED FOR SINK, ICE MAKERS, FRIDGE/ |
| FREEZER, DRINKING FOUNTAIN. FBC-ACC 306, 306, 804. |
| 3) PER WPB FBC 107.2.1, ARCHITECT TO PROVIDE A DETAIL |
| FOR THE DRINKING FOUNTAIN ON ARCHITECTURAL PLAN SHEETS |
| PERTAINING TO THE SECOND FLOOR RENOVATION FOR WHICH IS |
| APPLICABLE TO PERMIT 20010978, SHOWING COMPLIANCE WITH |
| FBC ACC 307 AND 602. |
| 4) RE: P0.1; THE FIXTURE PLUMBING SCHEDULE APPEARS TO |
| APPLY TO OTHER RENOVATIONS IN ADDITION TO THE SECOND |
| FLOOR RENOVATION. PER FBC 107.2.1, INDICATE ON THE |
| PLUMBING FIXTURE SCHEDULE THAT S-1 AND NOT S-2 IS |
| APPLICABLE TO THE SECOND FLOOR RENOVATION. |
| 6) RE: P0.1; TYPICAL PLUMBING FIXTURE CONNECTION |
| SCHEDULE. PLEASE COMPLY WITH THE FOLLOWING: |
| A. COFFEE MAKER; PROVIDE BACKFLOW PREVENTOR FOR WATER |
| CONNECTION |
| B. FILTER; PROVIDE MANUFACTURER'S SPECIFICATION AND |
| INSTALLATION MANUAL. |
| 1. IF RO SYSTEM IS PROVIDED THEN A BACKFLOW PREVENTOR |
| SHALL BE REQUIRED FOR THE WATER CONNECTION AND A |
| TRAPPED AND VENTED ACCESSIBLE OPEN RECEPTACLE SHALL BE |
| REQUIRED FOR THE DRAIN WHICH SHALL DISCHARGE TO THE |
| OPEN RECEPTACLE THROUGH AN AIR GAP. THIS INFORMATION |
| SHALL BE SHOWN IN PIPING ARRANGEMENT. |
| 2. IF A REMOVABLE/REPLACEMENT TYPE FILTER IS PROVIDED, |
| A BACKFLOW PREVENTER SHALL BE REQUIRED FOR THE WATER |
| CONNECTION. |
| C. REFRIGERATOR; PROVIDE BACKFLOW PREVENTOR FOR WATER |
| CONNECTION |
| 7) PER WPB FBC 107.2.1, PROVIDE WATER AND SANITARY |
| RISER DIAGRAMS FOR THE PLUMBING WORK SHOWN IN PLAN |
| VIEW. PLEASE NOTE THAT AN AAV SHALL NOT BE PERMITTED AS |
| A FIXTURE VENT PER FBC PL 918.3.1 UNLESS THE HORIZONTAL |
| BRANCH IS PROVIDED WITH A RELIEF VENT THAT CONNECTS TO |
| THE VENT STACK. |
| 8) IF DRINKING FOUNTAIN IS TO BE RELOCATED IN ORDER TO |
| COMPLY WITH THE REQUIREMENTS OF FBC ACC 307 AND 602, |
| THEN PER WPB FBC 107.2.1, PROVIDE PLAN VIEW AND RISER |
| DIAGRAMS FOR THE REQUIRED PIPING. |
| |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |