Plan Review Notes
Plan Review Notes For Permit 20010978
Permit Number 20010978
Review Stop P
Sequence Number 2
Notes
Date Text
2020-04-09 09:19:14REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20010978 505 S FLAGLER DR # 200
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 PLEASE NOTE: PLAN SHEETS A1.2.1 AND A1.3.1 WHICH WERE
 REFERENCED IN THE RESPONSE LETTER DATED 4/2/2020, DO
 NOT PERTAIN TO PERMIT 20010978 WHICH IS FOR WORK TO BE
 DONE ON THE SECOND FLOOR.
 1) PER WPB FBC 107.2.1, PROVIDE LOCATION OF THE
 REQUIRED BI-LEVEL DRINKING FOUNTAIN CALLED OUT IN
 PLUMBING FIXTURE SCHEDULE NOTED ON PLAN SHEET P0.1.
 ARCHITECT TO PROVIDE ADEQUATE SPACE FOR SAID DRINKING
 FOUNTAIN, WHICH SHALL BE CLEARLY SHOWN AS THE REQUIRED
 BI-LEVEL DRINKING FOUNTAIN ON ARCHITECTURAL PLAN SHEETS
 PERTAINING TO THE SECOND FLOOR RENOVATION FOR WHICH IS
 APPLICABLE TO PERMIT 20010978, THAT WILL COMPLY WITH
 THE REQUIREMENTS OF FBC ACC CHAPTERS 3 AND 6.
 ADDITIONALLY, THE DRINKING FOUNTAIN, WHICH SHALL BE
 CLEARLY SHOWN AS THE REQUIRED BI-LEVEL DRINKING
 FOUNTAIN ON PLAN SHEET P2.1.
 2) PER WPB FBC 107.2.1, ARCHITECT TO PROVIDE ON
 ARCHITECTURAL PLAN SHEETS PERTAINING TO THE SECOND
 FLOOR RENOVATION FOR WHICH IS APPLICABLE TO PERMIT
 20010978, CLEAR FLOOR SPACES, REACH RANGES, AND TURNING
 SPACES AS REQUIRED FOR SINK, ICE MAKERS, FRIDGE/
 FREEZER, DRINKING FOUNTAIN. FBC-ACC 306, 306, 804.
 3) PER WPB FBC 107.2.1, ARCHITECT TO NOTE ON
 ARCHITECTURAL PLAN SHEETS PERTAINING TO THE SECOND
 FLOOR RENOVATION FOR WHICH IS APPLICABLE TO PERMIT
 20010978, THAT PER FBC ACC 606.3, THE SINK AND
 SUBSEQUENT COUNTER/WORKING SPACE SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES ABOVE THE FINISH FLOOR.
 4) PER WPB FBC 107.2.1, ARCHITECT TO PROVIDE A DETAIL
 FOR THE DRINKING FOUNTAIN ON ARCHITECTURAL PLAN SHEETS
 PERTAINING TO THE SECOND FLOOR RENOVATION FOR WHICH IS
 APPLICABLE TO PERMIT 20010978, SHOWING COMPLIANCE WITH
 FBC ACC 307 AND 602.
 5) RE: P0.1; THE FIXTURE PLUMBING SCHEDULE APPEARS TO
 APPLY TO OTHER RENOVATIONS IN ADDITION TO THE SECOND
 FLOOR RENOVATION. PER FBC 107.2.1, INDICATE ON THE
 PLUMBING FIXTURE SCHEDULE THAT S-1 AND NOT S-2 IS
 APPLICABLE TO THE SECOND FLOOR RENOVATION.
 6) RE: P0.1; TYPICAL PLUMBING FIXTURE CONNECTION
 SCHEDULE. PLEASE COMPLY WITH THE FOLLOWING:
 A. COFFEE MAKER; PROVIDE BACKFLOW PREVENTOR FOR WATER
 CONNECTION
 B. FILTER; PROVIDE MANUFACTURER?S SPECIFICATION AND
 INSTALLATION MANUAL.
 1. IF RO SYSTEM IS PROVIDED THEN A BACKFLOW PREVENTOR
 SHALL BE REQUIRED FOR THE WATER CONNECTION AND A
 TRAPPED AND VENTED ACCESSIBLE OPEN RECEPTACLE SHALL BE
 REQUIRED FOR THE DRAIN WHICH SHALL DISCHARGE TO THE
 OPEN RECEPTACLE THROUGH AN AIR GAP. THIS INFORMATION
 SHALL BE SHOWN IN PIPING ARRANGEMENT.
 2. IF A REMOVABLE/REPLACEMENT TYPE FILTER IS PROVIDED,
 A BACKFLOW PREVENTER SHALL BE REQUIRED FOR THE WATER
 CONNECTION.
 C. REFRIGERATOR; PROVIDE BACKFLOW PREVENTOR FOR WATER
 CONNECTION
 7) PER WPB FBC 107.2.1, PROVIDE WATER AND SANITARY
 RISER DIAGRAMS FOR THE PLUMBING WORK SHOWN IN PLAN
 VIEW. PLEASE NOTE THAT AN AAV SHALL NOT BE PERMITTED AS
 A FIXTURE VENT PER FBC PL 918.3.1 UNLESS THE HORIZONTAL
 BRANCH IS PROVIDED WITH A RELIEF VENT THAT CONNECTS TO
 THE VENT STACK.
 8) IF DRINKING FOUNTAIN IS TO BE RELOCATED IN ORDER TO
 COMPLY WITH THE REQUIREMENTS OF FBC ACC 307 AND 602,
 THEN PER WPB FBC 107.2.1, PROVIDE PLAN VIEW AND RISER
 DIAGRAMS FOR THE REQUIRED PIPING
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH