2020-04-09 09:19:14 | REVIEWED BY JERRY SMITH. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20010978 505 S FLAGLER DR # 200 |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| PLEASE NOTE: PLAN SHEETS A1.2.1 AND A1.3.1 WHICH WERE |
| REFERENCED IN THE RESPONSE LETTER DATED 4/2/2020, DO |
| NOT PERTAIN TO PERMIT 20010978 WHICH IS FOR WORK TO BE |
| DONE ON THE SECOND FLOOR. |
| 1) PER WPB FBC 107.2.1, PROVIDE LOCATION OF THE |
| REQUIRED BI-LEVEL DRINKING FOUNTAIN CALLED OUT IN |
| PLUMBING FIXTURE SCHEDULE NOTED ON PLAN SHEET P0.1. |
| ARCHITECT TO PROVIDE ADEQUATE SPACE FOR SAID DRINKING |
| FOUNTAIN, WHICH SHALL BE CLEARLY SHOWN AS THE REQUIRED |
| BI-LEVEL DRINKING FOUNTAIN ON ARCHITECTURAL PLAN SHEETS |
| PERTAINING TO THE SECOND FLOOR RENOVATION FOR WHICH IS |
| APPLICABLE TO PERMIT 20010978, THAT WILL COMPLY WITH |
| THE REQUIREMENTS OF FBC ACC CHAPTERS 3 AND 6. |
| ADDITIONALLY, THE DRINKING FOUNTAIN, WHICH SHALL BE |
| CLEARLY SHOWN AS THE REQUIRED BI-LEVEL DRINKING |
| FOUNTAIN ON PLAN SHEET P2.1. |
| 2) PER WPB FBC 107.2.1, ARCHITECT TO PROVIDE ON |
| ARCHITECTURAL PLAN SHEETS PERTAINING TO THE SECOND |
| FLOOR RENOVATION FOR WHICH IS APPLICABLE TO PERMIT |
| 20010978, CLEAR FLOOR SPACES, REACH RANGES, AND TURNING |
| SPACES AS REQUIRED FOR SINK, ICE MAKERS, FRIDGE/ |
| FREEZER, DRINKING FOUNTAIN. FBC-ACC 306, 306, 804. |
| 3) PER WPB FBC 107.2.1, ARCHITECT TO NOTE ON |
| ARCHITECTURAL PLAN SHEETS PERTAINING TO THE SECOND |
| FLOOR RENOVATION FOR WHICH IS APPLICABLE TO PERMIT |
| 20010978, THAT PER FBC ACC 606.3, THE SINK AND |
| SUBSEQUENT COUNTER/WORKING SPACE SHALL BE INSTALLED |
| WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| SURFACE 34 INCHES ABOVE THE FINISH FLOOR. |
| 4) PER WPB FBC 107.2.1, ARCHITECT TO PROVIDE A DETAIL |
| FOR THE DRINKING FOUNTAIN ON ARCHITECTURAL PLAN SHEETS |
| PERTAINING TO THE SECOND FLOOR RENOVATION FOR WHICH IS |
| APPLICABLE TO PERMIT 20010978, SHOWING COMPLIANCE WITH |
| FBC ACC 307 AND 602. |
| 5) RE: P0.1; THE FIXTURE PLUMBING SCHEDULE APPEARS TO |
| APPLY TO OTHER RENOVATIONS IN ADDITION TO THE SECOND |
| FLOOR RENOVATION. PER FBC 107.2.1, INDICATE ON THE |
| PLUMBING FIXTURE SCHEDULE THAT S-1 AND NOT S-2 IS |
| APPLICABLE TO THE SECOND FLOOR RENOVATION. |
| 6) RE: P0.1; TYPICAL PLUMBING FIXTURE CONNECTION |
| SCHEDULE. PLEASE COMPLY WITH THE FOLLOWING: |
| A. COFFEE MAKER; PROVIDE BACKFLOW PREVENTOR FOR WATER |
| CONNECTION |
| B. FILTER; PROVIDE MANUFACTURER?S SPECIFICATION AND |
| INSTALLATION MANUAL. |
| 1. IF RO SYSTEM IS PROVIDED THEN A BACKFLOW PREVENTOR |
| SHALL BE REQUIRED FOR THE WATER CONNECTION AND A |
| TRAPPED AND VENTED ACCESSIBLE OPEN RECEPTACLE SHALL BE |
| REQUIRED FOR THE DRAIN WHICH SHALL DISCHARGE TO THE |
| OPEN RECEPTACLE THROUGH AN AIR GAP. THIS INFORMATION |
| SHALL BE SHOWN IN PIPING ARRANGEMENT. |
| 2. IF A REMOVABLE/REPLACEMENT TYPE FILTER IS PROVIDED, |
| A BACKFLOW PREVENTER SHALL BE REQUIRED FOR THE WATER |
| CONNECTION. |
| C. REFRIGERATOR; PROVIDE BACKFLOW PREVENTOR FOR WATER |
| CONNECTION |
| 7) PER WPB FBC 107.2.1, PROVIDE WATER AND SANITARY |
| RISER DIAGRAMS FOR THE PLUMBING WORK SHOWN IN PLAN |
| VIEW. PLEASE NOTE THAT AN AAV SHALL NOT BE PERMITTED AS |
| A FIXTURE VENT PER FBC PL 918.3.1 UNLESS THE HORIZONTAL |
| BRANCH IS PROVIDED WITH A RELIEF VENT THAT CONNECTS TO |
| THE VENT STACK. |
| 8) IF DRINKING FOUNTAIN IS TO BE RELOCATED IN ORDER TO |
| COMPLY WITH THE REQUIREMENTS OF FBC ACC 307 AND 602, |
| THEN PER WPB FBC 107.2.1, PROVIDE PLAN VIEW AND RISER |
| DIAGRAMS FOR THE REQUIRED PIPING |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-246-0882 MOBILE |
| |