2020-02-12 14:32:39 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #20010971 |
| 2/12/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M2.2 & M2.3: PER KEY NOTE #1, PLEASE PROVIDE |
| MINIMUM VENTILATION CALCULATIONS FOR ALL OCCUPIED ROOMS |
| AND SPACES- TABLE 403.3.1.1 FBC M. |
| |
| 2) M2.2: PROVIDE AN ACCESS PANEL FOR VAV 6- SECTION |
| 306.1 FBC M. |
| |
| 3) M2.3: PROVIDE ACCESS PANELS FOR VAV 16 & 17- SECTION |
| 306.1 FBC M. |
| |
| 4) M2.2, M2.3 & M6.1: HEAT IS REQUIRED FOR ALL ROOMS |
| AND SPACES PER SECTION 309.1. VERIFY A TEMPERATURE OF |
| 68 DEGREES F WILL BE MAINTAINED IN THE ROOMS SUPPLIED |
| BY VAV'S 9, 10, 11, 12 15, 17, 18, & 20. |
| |
| 5) PROVIDE NOTES ON THE PLANS TO INDICATE HOW THE HVAC |
| SYSTENS WILL BE PROTECTED DURING DEMOLITION AND |
| CONSTRUCTION- REFER TO SMACNA IAQ GUIDELINES- MERV 8 |
| FILTERS ARE REQUIRED AT ALL RETURN AIR GRILLS LOCATED |
| IN AREAS OF DEMOLITION AND CONSTRUCTION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE |
| RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. |
| THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |