Plan Review Notes For Permit 20010904 |
Permit Number |
20010904 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-01-23 06:24:51 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW DENIED: | | | | FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN | | OF 30' OR GREATER IN ANY DIRECTION: | | | | A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE | | BASEPLATE/TIEDOWN DETAILS. | | B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. | | | | THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY | | A DESIGN PROFESSIONAL. |
|