Plan Review Notes
Plan Review Notes For Permit 20010871
Permit Number 20010871
Review Stop M
Sequence Number 3
Notes
Date Text
2020-03-25 08:00:01***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 3RD MECHANICAL REVIEW DENIED:
  
 REFER TO SECTION M1602.3 BALANCED RETURN AIR. 2017
 RESIDENTIAL CODE.
 THE CFMS SHOWN ON THE PLANS COMPARED WITH THE CFMS
 FROM THE A/C UNIT, AS SHOWN ON THE ENERGY CALCULATIONS,
 ARE NOT BALANCED, THE SUBMITTED PLAN INDICATES A TOTAL
 OF 1,160 CFM OF SUPPLY AIR AND THE ENERGY CALCULATIONS
 INDICATE 750 CFM.
  