Plan Review Notes For Permit 20010871 |
Permit Number |
20010871 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-03-25 08:00:01 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561?805?6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | 3RD MECHANICAL REVIEW DENIED: | | | | REFER TO SECTION M1602.3 BALANCED RETURN AIR. 2017 | | RESIDENTIAL CODE. | | THE CFMS SHOWN ON THE PLANS COMPARED WITH THE CFMS | | FROM THE A/C UNIT, AS SHOWN ON THE ENERGY CALCULATIONS, | | ARE NOT BALANCED, THE SUBMITTED PLAN INDICATES A TOTAL | | OF 1,160 CFM OF SUPPLY AIR AND THE ENERGY CALCULATIONS | | INDICATE 750 CFM. | | |
|