 2ND MECHANICAL REVIEW DENIED:
  
  
 1) OK
  
 2) REFER TO SECTION M1602.3 BALANCED RETURN AIR. 2017
 RESIDENTIAL CODE.
 (THE CFMS SHOWN ON THE PLANS COMPARED WITH THE CFMS
 FROM THE A/C UNIT, AS SHOWN ON THE ENERGY CALCULATIONS,
 ARE NOT BALANCED.)
  
 3) ADDRESS ON PLAN AND APPLICATION DO NOT MATCH.
 (THE PLANS NEED TO HAVE THE SAME ADDRESS AS THE
 APPLICATION.)
  