Plan Review Notes For Permit 20010870 |
Permit Number |
20010870 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-02-21 09:03:45 | PLUMBING 1ST REVIEW**DENIED**20010807 | | 1) PROVIDE OCCUPANT LOAD AS I AM UNABLE TO LOCATE IT. | | FBC 107.3.5 | | 2) PLEASE PROVIDE WHICH (A) OCCUPANCY THIS PROJECT IS. | | EXAMPLE A-1, A-2, A-3 ETC. FBC 107.3.5 | | 3) PROVIDE MIN FIXTURE REQUIREMENTS AS PER 403.1. FBC | | 107.3.5 | | 4) SHT. A-1.5 PLEASE CLARIFY THE MIN 28?MIN YOU CALL | | OUT BETWEEN THE TOILET AND SINK. IF THE TOILET WAS SET | | IN THIS LOCATION YOU WOULD NEVER MEET THE 60? CLEAR | | FLOOR SPACE REQUIREMENT PER FBC-ACC 604.3.1 | | 5) PROVIDE CAF? SINK ACCESSIBILITY DETAILS. (A) CLEAR | | FLOOR SPACE FBC-ACC 804.3.1 AND SHOW THE MAX COUNTER | | TOP HEIGHT OF 34? FBC-ACC 804.3.2 | | 6) SHT. P601 THE PRINT IS TOO LIGHT UNABLE TO READ | | PIPING SIZE. FBC 107.2 | | 7) IT APPEARS FROM THE TOILET?S PROVIDE FOR EACH SEX | | YOU HAVE NOT MEET POTTY PARITY. FBC-PLB 403.1.3 PLEASE | | CLARIFY. | | | | | | TIM HUNT | | PLUMBING PLAN REVIEW | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | 561-248-2703 | | [email protected] | | | | |
|