Date Text
2020-02-21 09:03:45PLUMBING 1ST REVIEW**DENIED**20010807
 1) PROVIDE OCCUPANT LOAD AS I AM UNABLE TO LOCATE IT.
 FBC 107.3.5
 2) PLEASE PROVIDE WHICH (A) OCCUPANCY THIS PROJECT IS.
 EXAMPLE A-1, A-2, A-3 ETC. FBC 107.3.5
 3) PROVIDE MIN FIXTURE REQUIREMENTS AS PER 403.1. FBC
 107.3.5
 4) SHT. A-1.5 PLEASE CLARIFY THE MIN 28?MIN YOU CALL
 OUT BETWEEN THE TOILET AND SINK. IF THE TOILET WAS SET
 IN THIS LOCATION YOU WOULD NEVER MEET THE 60? CLEAR
 FLOOR SPACE REQUIREMENT PER FBC-ACC 604.3.1
 5) PROVIDE CAF? SINK ACCESSIBILITY DETAILS. (A) CLEAR
 FLOOR SPACE FBC-ACC 804.3.1 AND SHOW THE MAX COUNTER
 TOP HEIGHT OF 34? FBC-ACC 804.3.2
 6) SHT. P601 THE PRINT IS TOO LIGHT UNABLE TO READ
 PIPING SIZE. FBC 107.2
 7) IT APPEARS FROM THE TOILET?S PROVIDE FOR EACH SEX
 YOU HAVE NOT MEET POTTY PARITY. FBC-PLB 403.1.3 PLEASE
 CLARIFY.
  
  
 TIM HUNT
 PLUMBING PLAN REVIEW
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 561-248-2703
 [email protected]
  
  