Plan Review Notes
Plan Review Notes For Permit 20010870
Permit Number 20010870
Review Stop M
Sequence Number 1
Notes
Date Text
2020-02-18 09:04:311ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010870
 2/18/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M701, M801, & M802: THE PRINT ON THESE PLAN
 SHEETS IS TOO FAINT TO READ AND IS ILLEGIBLE. PLEASE
 PROVIDE CLEAR PLANS FOR REVIEW- SECTION 107.2.1 WPB.
  
 2) M101: EXHAUST VENTILATION AT A RATE OF 1.0 CFMS PER
 SQUARE FOOT IS REQUIRED FOR THE LAB. PLEASE REFER TO
 SECTIONS 510.1 & 510.2 FBC M AND PROVIDE A NARRATIVE TO
 CLARIFY THE PROCESSES THAT OCCUR IN THE LAB.
  
 3) M101 & M701: PROVIDE EQUIPMENT SCHEDULES FOR THE
 EXISTING FAN COIL UNITS- SECTION 107.2.1 WPB.
  
 4) M101 & M701: REFER TO SECTION 809.2 FBC EX AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS
 AND SPACES PER TABLE 403.3.1.1 FBC M. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS
 OF OUTDOOR AIR.
  
 5) M101: AUTOMATIC SHUTOFF DAMPERS, EITHER MOTORIZED OR
 GRAVITY, SHALL BE PROVIDED FOR O/A DUCTS SUPPLYING EACH
 FAN COIL UNIT- SECTION C403.2.4.3 FBC EC.
  
 6) M101: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY SYSTEMS OF THE EXISTING FAN COIL UNITS- SECTION
 606.2.1 FBC M. PLEASE PROVIDE A SYMBOL AT ALL REQUIRED
 LOCATIONS AND INDICATE HOW THE DEVICES WILL BE
 SUPERVISED- SECTION 606.4.1 FBC M.
  
 7) M101: RETURN GRILLS NOT SHOWN IN MANY OF THE ROOMS
 AND SPACES- SECTIONS 601.5 & 601.6 FBC M.
  
 8) M101: PROVIDE AN EQUIPMENT PLAN AND SCHEDULE FOR THE
 CAFE. CLARIFY IF AN COOKING OPERATIONS WILL OCCUR THERE
 AND IF ANY COOKING APPLIANCES ARE TO BE INSTALLED-
 SECTION 107.2.1 WPB. PLEASE NOTE THAT EXHAUST
 VENTILATION MAY BE REQUIRED PER TABLE 403.3.1.1 AND
 SECTION 506 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  