2020-02-18 09:04:31 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #20010870 |
| 2/18/20 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS M701, M801, & M802: THE PRINT ON THESE PLAN |
| SHEETS IS TOO FAINT TO READ AND IS ILLEGIBLE. PLEASE |
| PROVIDE CLEAR PLANS FOR REVIEW- SECTION 107.2.1 WPB. |
| |
| 2) M101: EXHAUST VENTILATION AT A RATE OF 1.0 CFMS PER |
| SQUARE FOOT IS REQUIRED FOR THE LAB. PLEASE REFER TO |
| SECTIONS 510.1 & 510.2 FBC M AND PROVIDE A NARRATIVE TO |
| CLARIFY THE PROCESSES THAT OCCUR IN THE LAB. |
| |
| 3) M101 & M701: PROVIDE EQUIPMENT SCHEDULES FOR THE |
| EXISTING FAN COIL UNITS- SECTION 107.2.1 WPB. |
| |
| 4) M101 & M701: REFER TO SECTION 809.2 FBC EX AND |
| PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS |
| AND SPACES PER TABLE 403.3.1.1 FBC M. PROVIDE A |
| SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS |
| OF OUTDOOR AIR. |
| |
| 5) M101: AUTOMATIC SHUTOFF DAMPERS, EITHER MOTORIZED OR |
| GRAVITY, SHALL BE PROVIDED FOR O/A DUCTS SUPPLYING EACH |
| FAN COIL UNIT- SECTION C403.2.4.3 FBC EC. |
| |
| 6) M101: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| SUPPLY SYSTEMS OF THE EXISTING FAN COIL UNITS- SECTION |
| 606.2.1 FBC M. PLEASE PROVIDE A SYMBOL AT ALL REQUIRED |
| LOCATIONS AND INDICATE HOW THE DEVICES WILL BE |
| SUPERVISED- SECTION 606.4.1 FBC M. |
| |
| 7) M101: RETURN GRILLS NOT SHOWN IN MANY OF THE ROOMS |
| AND SPACES- SECTIONS 601.5 & 601.6 FBC M. |
| |
| 8) M101: PROVIDE AN EQUIPMENT PLAN AND SCHEDULE FOR THE |
| CAFE. CLARIFY IF AN COOKING OPERATIONS WILL OCCUR THERE |
| AND IF ANY COOKING APPLIANCES ARE TO BE INSTALLED- |
| SECTION 107.2.1 WPB. PLEASE NOTE THAT EXHAUST |
| VENTILATION MAY BE REQUIRED PER TABLE 403.3.1.1 AND |
| SECTION 506 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |