Plan Review Notes
Plan Review Notes For Permit 20010869
Permit Number 20010869
Review Stop E
Sequence Number 1
Notes
Date Text
2020-01-26 13:25:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 2. PROVIDE DETAIL SHOWING ALL ELECTRIAL CONNECTIONS
 INSTALLED ABOVE THE ELECTRICAL DATUM PLANE. NEC 555.9,
 555.5
 3. PROVIDE GROUND FAULT PROTECTION. NEC 555.3
 4. RISER DIAGRAM SHOWS A #6 EQUIPMENT GROUNDING
 CONDUCTOR INSTALLED IN THE FPL FEED TO THE METER CAN.
 THIS CONDUIT SHOULD NOT INCLUDE AN EGC. PROVIDE
 CORRECTION. NEC 250.6, 250.24
 5. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN
 THE FBC ENERGY CONSERVATION. FBC EC C405.2.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  