2020-01-27 16:34:251ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010803
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: IT APPEARS THAT FIRE DAMPERS ARE MISSING
 WHERE SUPPLY DUCTS ARE PENETRATING THE CONTROL ROOM
 WALLS- SECTION 607.5.2 FBC M.
  
 2) M-1 & LS1.0: PROVIDE DETAILS FOR VENTING OF THE CT
 SCAN IF REQUIRED BY MANUFACTURER'S SPECIFICATIONS. SHOW
 THE TYPE AND SIZE OF VENT, VENT RUN AND TERMINATION
 LOCATION- SECTION 304.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  