2020-01-23 14:47:37 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| 805-6724 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| 1. FBC EB 504.1 REVISE DRAWINGS TO REFLECT LEVEL 2 |
| ALTERATION. |
| 2. FBC EB 801.1 & 801.2 LEVEL 2 ALTERATIONS AS |
| DESCRIBED IN SECTION 504 SHALL COMPLY WITH THE |
| REQUIREMENTS OF CHAPTER 8. IN ADDITION TO THE |
| REQUIREMENTS OF THIS CHAPTER, ALL WORK SHALL COMPLY |
| WITH THE REQUIREMENTS OF CHAPTER 7. |
| 3. FBC B 107.2.1 PROVIDE FRAMING DETAILS SUPPLIED FOR |
| ALL NEW WALLS/CEILINGS/INFILLS/SOFFITS. SHOW ANCHORAGE, |
| BRACING AND BLOCKING |
| |