2020-01-21 08:19:53 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| 805-6724 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| 1.FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF |
| PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN |
| HEADING ?SPECIFIC ANCHOR TYPE?; PROVIDE INFORMATION |
| FROM PAGE 13 OF FL1850-R11. EXAMPLE: ALL POINTS SOLID |
| SET ANCHORS ARE NOT ALLOWED IN CONNECTION TYPES A, D OR |
| G IN POURED CONCRETE OR CONCRETE BLOCK. COLUMN HEADING |
| ?ANCHOR SPACING? PLEASE VERIFY ANCHOR SPACING AS PER |
| SPECIFIC ANCHOR TYPE USED. |
| 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE |
| NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON |
| SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF |
| USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON |
| W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR). |
| REDUCE ANCHOR SPACING BY MUTIPLYING SPACING SHOWN ON |
| SCHEDULE BY THE FACTOR |
| |