 1) PENINSULAR SPACE HAS AN OVERHANG THAT LOOKS TO BE
 MORE THAN 6" THE OUTLET MOUNTED BELOW WOULD NOT MEET
 THE REQUIREMENTS OF THE RECEPTACLE SPACING.
  
 E3901.4.5 RECEPTACLE OUTLET LOCATION.
 RECEPTACLE OUTLETS SHALL BE LOCATED NOT MORE THAN 20
 INCHES (508 MM) ABOVE THE COUNTERTOP. RECEPTACLE OUTLET
 ASSEMBLIES INSTALLED IN COUNTERTOPS SHALL BE LISTED FOR
 THE APPLICATION. RECEPTACLE OUTLETS SHALL NOT BE
 INSTALLED IN A FACE-UP POSITION IN THE WORK SURFACES OR
 COUNTERTOPS. RECEPTACLE OUTLETS RENDERED NOT READILY
 ACCESSIBLE BY APPLIANCES FASTENED IN PLACE, APPLIANCE
 GARAGES, SINKS OR RANGETOPS AS ADDRESSED IN THE
 EXCEPTION TO SECTION E3901.4.1, OR APPLIANCES OCCUPYING
 DEDICATED SPACE SHALL NOT BE CONSIDERED AS THESE
 REQUIRED OUTLETS. [210.52(C)(5)]
  
 EXCEPTION: RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE
 MOUNTED NOT MORE THAN 12 INCHES (305 MM) BELOW THE
 COUNTERTOP IN CONSTRUCTION DESIGNED FOR THE PHYSICALLY
 IMPAIRED AND FOR ISLAND AND PENINSULAR COUNTERTOPS
 WHERE THE COUNTERTOP IS FLAT ACROSS ITS ENTIRE SURFACE
 AND THERE ARE NO MEANS TO MOUNT A RECEPTACLE WITHIN 20
 INCHES (508 MM) ABOVE THE COUNTERTOP, SUCH AS IN AN
 OVERHEAD CABINET. RECEPTACLES MOUNTED BELOW THE
 COUNTERTOP IN ACCORDANCE WITH THIS EXCEPTION SHALL NOT
 BE LOCATED WHERE THE COUNTERTOP EXTENDS MORE THAN 6
 INCHES (152 MM) BEYOND ITS SUPPORT BASE. [210.52(C)(5)
 EXCEPTION]