Plan Review Notes
Plan Review Notes For Permit 20010577
Permit Number 20010577
Review Stop B
Sequence Number 1
Notes
Date Text
2020-02-05 18:23:00RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 2- IT IS NOT CLEAR EXACT LOCATION OF THE PROPOSED
 ADDITION. SETBACKS SHOWN ON THE SURVEY AND SETBACKS
 SHOWN ON THE SITE PLAN ON SHEET SP-1 DON'T MATCH.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE/CORRECT INFORMATION ON TOP OF FORM.
 PROVIDE THE NAME OF THE OWNER AND PROVIDE CORRECT NAME
 OF THE BUILDER. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B) THE AREA WEIGHTED AVERAGE SHGC SHOWN ON ITEM #7 ON
 PAGE 1 OF 4 DOESN'T COMPLY WITH THE MAXIMUM
 FENESTRATION SHGC REQUIRED BY SEC. R405.5.3.4 OF
 FBC-ENERGY CONSERVATION. THE MAXIMUM AREA WEIGHTED
 AVERAGE FENESTRATION SHGC ALLOWED IS 0.50. ENERGY
 CALCULATIONS SUBMITTED SHOW 0.70. REVISE AS REQUIRED TO
 COMPLY.
  
 C)PAGE 2 OF 4 UNDER SPACES INDICATES THAT THERE IS A
 KITCHEN IN THE ADDITION. ZONING DOESN'T ALLOW THE
 KITCHEN. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 D) REVISE DOOR INFORMATION PAGE 3 OF 4. THERE ARE NOT
 WOOD DOORS. SEE PLANS AND PRODUCT APPROVAL AND REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 4- WALL SECTION #2 ON SHEET A-2:
 A) NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS
 AS REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL ON THE
 WOOD FRAMED WALL.
  
 B) NEED TO SPECIFY THE 7/8" MIN. STUCCO THICKNESS AS
 REQUIRED BY TABLE R702.1(1) FBC-RESIDENTIAL.
  
 5- REVISE ATTIC ACCESS LOCATION. NEED TO PROVIDE AT
 LEAST 30 INCHES OF HEADROOM CLEARANCE AS REQUIRED BY
 SEC. R807 FBC-RESIDENTIAL
  
 6- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806
 FBC-RESIDENTIAL. SPECIFY SIZE OF GABLE END VENTS SHOWN
 ON THE EXTERIOR ELEVATIONS AND CLEARLY SPECIFY IF THERE
 ARE VENTS LOCATED ON THE SOFFIT (SPECIFY SIZE AND
 SPACING).
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A) GABLE END VENTS AS SHOWN ON EXTERIOR ELEVATIONS.
  
 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 9- REVISE THE SIZE OF THE STRUCTURAL BUCK SPECIFIED ON
 ON DETAIL C AND E ON SHEET A-2. STRUCTURAL BUCK NEEDS
 TO PROVIDE FULL SUPPORT TO THE DOOR FRAME AND NEED TO
 EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME AS REQUIRED BY SEC. R609.7.2.1 FBC-RESIDENTIAL.
 2X4 BUCK IS SMALLER THAN THE DOOR FRAME. REVISE AS
 REQUIRED.
  
 10- TRUSS PACKAGE SUBMITTED:
 A) TRUSSES WERE DESIGNED BASED ON BUILDING EXPOSURE B.
 THIS DOESN'T MATCH THE ARCHITECT'S WIND DESIGN CRITERIA
 ON SHEET A-2. TRUSS ENGINEER TO REVISE AS REQUIRED.
 SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) TRUSS LOADING SPECIFICATIONS DON'T MATCH ARCHITECT'S
 LOADING LOADING SPECIFICATIONS
 ON THE ROOF FRAMING NOTES ON SHEET S-1. TRUSS ENGINEER
 TO REVISE AS REQUIRED TO MATCH.
 SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 C) ARCHITECT OF RECORD TO REVIEW/APPROVED THE TRUSS
 PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $48,011. THE
 PERMIT FEE BALANCE IS $1126.88.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]