2020-01-16 15:03:33FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 IS THIS A NEW SERVICE OR A REAIR.
  
 IF THIS IS NEW WHERE IS THE SERVICE THAT WAS JUST
 INSTALLED IN REFERENCE TO THIS NEW SERVICE??
  
 WE DON'T GIVE ADDITIONAL SERVICES TO A PROPERTY UNLESS
 THEY CAN MEET ONE OF THE REQUIREMENTS FROM 230.2
  
 230.2 NUMBER OF SERVICES
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY
 ONE SER VICE UNLESS PERMITTED IN 230.2(A) THROUGH (D).