Plan Review Notes
Plan Review Notes For Permit 20010495
Permit Number 20010495
Review Stop M
Sequence Number 1
Notes
Date Text
2020-02-05 09:45:10***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 MECHANICAL REVIEW DENIED:
  
 1. FBC R M 1401.1, 1401.2, 1401.3, PROVIDE THE
 MANUFACTURERS SPECIFICATIONS INCLUDING THE CFM
 CAPACITY.
 2. FBC R M 1411.3 PROVIDE DETAILS INCLUDING LOCATION OF
 CONDENSATE DISPOSAL DETAILS.
 3. FBC R M 1401.4/1401.5 PROVIDE THE MANUFACTURER'S
 SPECIFICATIONS FOR EXTERIOR CONDENSING UNIT ANCHORING
 DETAILS.
  