Plan Review Notes For Permit 20010495 |
Permit Number |
20010495 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-02-05 09:45:10 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | MECHANICAL REVIEW DENIED: | | | | 1. FBC R M 1401.1, 1401.2, 1401.3, PROVIDE THE | | MANUFACTURERS SPECIFICATIONS INCLUDING THE CFM | | CAPACITY. | | 2. FBC R M 1411.3 PROVIDE DETAILS INCLUDING LOCATION OF | | CONDENSATE DISPOSAL DETAILS. | | 3. FBC R M 1401.4/1401.5 PROVIDE THE MANUFACTURER'S | | SPECIFICATIONS FOR EXTERIOR CONDENSING UNIT ANCHORING | | DETAILS. | | |
|