2021-06-03 14:41:59 | FAILED |
| |
| PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| |
| ARCADE IDENTITY SIGN TYPE 1D |
| |
| PERMITTED: 97.5 SF |
| EXISTING AWING SIGNS (3): 6.03 SF |
| APPROVED BARRIO SANGRIA SIGN (PERMIT 19050032): 16.8 SF |
| PROPOSED SIGN: 23 SF |
| |
| TOTAL SIGN AREA: 45.83 SF |
| |
| 1) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE ALL |
| LIGHTING CONDUIT, WIRING, BALLAST BOXES, TRANSFORMERS, |
| AND OTHER EQUIPMENT NECESSARY FOR SIGN CONNECTION SHALL |
| BE CONCEALED AND NOT VISIBLE TO THE PUBLIC. THE HAND |
| DRAWING FROM THE ELECTRICAL CONTRA VERIFIES THAT THERE |
| WILL BE A BELL BOX WITH DISCONNECT SWITCH AND |
| ELECTRICAL LEAD WITHIN FLEXIBLE CONDUIT TO AN EXISTING |
| LIGHTING J BOX. THE ELECTRICIAN ADDED THE NOTE THAT THE |
| COVER WILL BE DONE BY OTHERS. UNTIL A PLAN IS SUBMITTED |
| SHOWING AND DETAILING EXACTLY HOW THE COVER TO CONCEAL |
| THE ELECTRICAL CONNECTIONS TO THIS ILLUMINATED SIGN, |
| ZONING WILL NOT APPROVE THIS PERMIT AS ALL OF THE |
| REQUIREMENTS OF THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA HAVE NOT BEEN MET. |
| |
| 2) ALTERNATIVELY YOU MAY REMOVE ALL REFERENCE TO |
| ILLUMINATION AND ELECTRIC, TO INCLUDE THE "SATIN BLACK |
| DIRECTIONAL BULLET SIGN LIGHTS" AND THE MOUNTING ARMS, |
| FROM THE PLANS INCLUDED WITH THE SIGN PERMIT. THESE |
| WILL THEN ALL NEED TO BE SHOWN IN DETAIL ON THE PLANS |
| WITH THE ELECTRIC PERMIT, THAT INCLUDES CONCEALMENT. IF |
| THE ELECTRIC PERMIT DOES NOT PASS, YOU WILL NOT BE |
| PERMITTED TO INSTALL THE BULLET SIGN LIGHT. |
| |
| NOTE: THE SIGN WITH NO ELECTRIC DOES MEET THE ROSEMARY |
| SQUARE TENANT SIGN CRITERIA. |
| |
| I HAVE SEPARATELY CONTACTED THE ROSEMARY SQUARE |
| MANAGEMENT REGARDING THE STATUS OF THIS PERMIT. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected]. |
| |