2021-03-30 13:12:58 | FAILED |
| |
| PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| |
| ARCADE IDENTITY SIGN TYPE 1D |
| |
| PERMITTED: 97.5 SF |
| EXISTING AWING SIGNS (3): 6.03 SF |
| APPROVED BARRIO SANGRIA SIGN (PERMIT 19050032): 16.8 SF |
| PROPOSED SIGN: 23 SF |
| |
| TOTAL SIGN AREA: 45.83 SF |
| |
| 1) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA REQUIRE ALL LIGHTING CONDUIT, WIRING, BALLAST |
| BOXES, TRANSFORMERS, AND OTHER EQUIPMENT NECESSARY FOR |
| SIGN CONNECTION SHALL BE CONCEALED AND NOT VISIBLE TO |
| THE PUBLIC. THE PROPOSED SIGN LIGHTING HAS AN EXPOSED |
| BELL BOX WITH DISCONNECT SWITCH AND ELECTRICAL LEAD |
| WITHIN FLEXIBLE CONDUIT, WHICH IS NOT PERMITTED. |
| ADDITIONALLY, NO INFORMATION IS PROVIDED AS TO HOW THE |
| ELECTRIC SERVICE IS PROVIDED TO THE BELL BOX. YOU ARE |
| SHOWING THE LIGHTING AS PART OF THIS PERMIT, SO IN |
| ACCORDANCE WITH THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA YOU NEED TO PROVIDE THE INFORMATION ON HOW THE |
| CONCEALMENT REQUIREMENT IS MET. YOU ARE NOT ALLOWED TO |
| DESIGN A SIGN WITH THE WIRING STUBBED OUT THAT THEN |
| REQUIRES NON-COMPLIANCE WITH THE CONCEALMENT |
| REQUIREMENT. IN THIS SPECIFIC CASE YOU MAY NOT REMOVE |
| THE ITEMS WHICH DID NOT COMPLY WITH THE ROSEMARY SQUARE |
| TENANT SIGN CRITERIA AND SIMPLY STATE IT WILL BE |
| PROVIDED WITH OTHERS. YOU NEED TO COORDINATE WITH THE |
| "OTHERS" WHO ARE PROVIDING THE ELECTRICAL PRIMARY AND |
| PROVIDE THIS INFORMATION ON THE PLANS TO VERIFY THAT |
| THE CONCEALMENT REQUIREMENTS ARE MET. THE PERMIT NUMBER |
| CITED (20061298) IN THE RESPONSE DOES NOT SHOW ANY |
| ELECTRICAL CONNECTION TO THE PROPOSED LOCATION OF THIS |
| SIGN. YOU ARE REQUIRED TO SHOW HOW THE ELECTRICAL TO |
| THE LIGHTING FOR THIS SIGN COMPLIES WITH THE ROSEMARY |
| SQUARE TENANT SIGN CRITERIA. ***** THE RESPONSE STATES |
| THAT THE SIGN PERMIT WILL NOT BE DOING ELECTRICAL WORK |
| AND THAT NO ELECTRICAL PERMIT WAS PULLED; HOWEVER, YOU |
| DID SUBMIT AN ELECTRICAL SUB PERMIT FOR THIS |
| INSTALLATION (PERMIT NUMBER 20010423). SINCE YOU HAVE |
| SUBMITTED AN ELECTRICAL SUB PERMIT FOR YOUR SIGN THAT |
| PROPOSES ELECTRIC, IN ACCORDANCE WITH THE ROSEMARY |
| SQUARE TENANT SIGN CRITERIA YOU NEED TO PROVIDE |
| DRAWINGS SHOWING THAT THE ELECTRIC MEETS THE REQUIRED |
| STANDARDS (AS REPEATED ON EACH PERMIT REVIEW). YOUR |
| OTHER OPTION IS TO REMOVE ALL REFERENCE TO ILLUMINATION |
| AND ELECTRIC, TO INCLUDE THE "SATIN BLACK DIRECTIONAL |
| BULLET SIGN LIGHTS" AND THE MOUNTING ARMS, FROM THE |
| SIGN PERMIT. THESE WILL THEN ALL NEED TO BE SHOWN IN |
| DETAIL ON THE ELECTRIC PERMIT. IF THE ELECTRIC PERMIT |
| DOES NOT PASS, YOU WILL NOT BE PERMITTED TO INSTALL THE |
| BULLET SIGN LIGHT. |
| |
| NOTE: THE SIGN WITH NO ELECTRIC DOES MEET THE ROSEMARY |
| SQUARE TENANT SIGN CRITERIA. |
| |