2021-02-08 15:40:03 | FAILED |
| |
| PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| |
| ARCADE IDENTITY SIGN TYPE 1D |
| |
| PERMITTED: 97.5 SF |
| EXISTING AWING SIGNS (3): 6.03 SF |
| APPROVED BARRIO SANGRIA SIGN (PERMIT 19050032): 16.8 SF |
| PROPOSED SIGN: 23 SF |
| |
| TOTAL SIGN AREA: 45.83 SF |
| |
| 1) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA REQUIRE ALL LIGHTING CONDUIT, WIRING, BALLAST |
| BOXES, TRANSFORMERS, AND OTHER EQUIPMENT NECESSARY FOR |
| SIGN CONNECTION SHALL BE CONCEALED AND NOT VISIBLE TO |
| THE PUBLIC. THE PROPOSED SIGN LIGHTING HAS AN EXPOSED |
| BELL BOX WITH DISCONNECT SWITCH AND ELECTRICAL LEAD |
| WITHIN FLEXIBLE CONDUIT, WHICH IS NOT PERMITTED. |
| ADDITIONALLY, NO INFORMATION IS PROVIDED AS TO HOW THE |
| ELECTRIC SERVICE IS PROVIDED TO THE BELL BOX. YOU ARE |
| SHOWING THE LIGHTING AS PART OF THIS PERMIT, SO IN |
| ACCORDANCE WITH THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA YOU NEED TO PROVIDE THE INFORMATION ON HOW THE |
| CONCEALMENT REQUIREMENT IS MET. YOU ARE NOT ALLOWED TO |
| DESIGN A SIGN WITH THE WIRING STUBBED OUT THAT THEN |
| REQUIRES NON-COMPLIANCE WITH THE CONCEALMENT |
| REQUIREMENT. IN THIS SPECIFIC CASE YOU MAY NOT REMOVE |
| THE ITEMS WHICH DID NOT COMPLY WITH THE ROSEMARY SQUARE |
| TENANT SIGN CRITERIA AND SIMPLY STATE IT WILL BE |
| PROVIDED WITH OTHERS. YOU NEED TO COORDINATE WITH THE |
| "OTHERS" WHO ARE PROVIDING THE ELECTRICAL PRIMARY AND |
| PROVIDE THIS INFORMATION ON THE PLANS TO VERIFY THAT |
| THE CONCEALMENT REQUIREMENTS ARE MET. ***** THE PERMIT |
| NUMBER CITED (20061298) IN THE RESPONSE NOT SHOW ANY |
| ELECTRICAL CONNECTION TO THE PROPOSED LOCATION OF THIS |
| SIGN. YOU ARE REQUIRED TO SHOW HOW THE ELECTRICAL TO |
| THE LIGHTING FOR THIS SIGN COMPLIES WITH THE ROSEMARY |
| SQUARE TENANT SIGN CRITERIA. |
| |
| 2) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA ALLOW A MAXIMUM HEIGHT FOR ARCADE IDENTITY |
| SIGNS OF 12 FEET FROM THE FINISHED FLOOR. THE SIGN |
| EXCEEDS THE 12 FOOT HEIGHT ALLOWANCE. 9 FEET + 4 FEET 8 |
| INCHES = 13 FEET 8 INCHES. THE RESPONSE MENTIONS THAT A |
| WAIVER HAS BEEN SUBMITTED TO ALLOW WHAT IS AN |
| ALTERNATIVE VERTICAL PLACEMENT OF A PERMITTED SIGN |
| (WAIVER I); HOWEVER, THE PERMIT RESUBMITTAL DOES NOT |
| INCLUDE THIS WAIVER I. |
| |