2020-12-02 14:56:13 | FAILED |
| |
| PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| |
| ARCADE IDENTITY SIGN TYPE 1D |
| |
| 1) THE ROSEMARY SQUARE TENANT SIGN CRITERIA PERMIT C.1 |
| PAINTED SIGN PANELS AND C.2 SIGNAGE ON THE FRONT AND |
| BACK OF A SUSPENDED PANEL ON A CASE BY CASE BASIS. |
| APPROVAL OF CASE BY CASE SIGN OPTIONS MAY BE APPROVED |
| BY CITYPLACE RETAIL AS A WAIVER I. PLEASE PROVIDE AN |
| UPDATED WAIVER I APPROVAL LETTER (OR ADDITIONAL LETTER) |
| THAT APPROVES THE TWO REQUESTED WAIVERS I. |
| |
| 2) THE ROSEMARY SQUARE SIGN PLAN MEASURES SIGNAGE |
| ALLOWANCE AS FOLLOWS - ONE SQUARE FOOT OF SIGNAGE FOR |
| EACH ONE LINEAR FOOT OF STORE FRONTAGE BASED ON THE |
| LEASE LINE DRAWING PROVIDED WITH THE RESUBMITTAL. THE |
| TOTAL AMOUNT OF SIGNAGE PERMITTED ON THIS FACADE IS |
| 97.5 SQUARE FEET. CITY CELLAR HAS EXISTING SIGNAGE ON |
| THE FACADE OF THE BUILDING AND THE AWNING VALANCES |
| WHICH COUNT TOWARD THE MAXIMUM PERMITTED SIGN SQUARE |
| FOOTAGE. PLEASE CLARIFY IF THE SIGNAGE WILL REMAIN |
| AFTER THE INSTALLATION OF THE PROPOSED ARCADE IDENTITY |
| SIGN. |
| |
| A. THE CITY CELLAR FAADE SIGN IS 49.5 SQUARE FEET |
| (BASED ON APPROVED PERMIT). IF THE FASCIA SIGN WILL |
| REMAIN, THEN ITS SQUARE FOOTAGE WILL BE DEDUCTED FROM |
| THE PERMITTED SIGNAGE AMOUNT. |
| |
| B. STAFF WAS UNABLE TO LOCATE THE SQUARE FOOTAGE OF THE |
| SIGNAGE ON THE THREE AWNINGS. IF THE AWNING SIGNS ARE |
| TO REMAIN, THEN YOU MUST PROVIDE THE TOTAL SQUARE |
| FOOTAGE OF THESE THREE AWNING SIGNS AND IT WILL BE |
| DEDUCTED FROM THE PERMITTED SIGNAGE AMOUNT. |
| |
| C. BARRIO SANGRIA HAS A PERMITTED 16.8 SQUARE FOOT SIGN |
| WHICH HAS NOT YET BEEN INSTALLED. SINCE THE SIGN FALLS |
| WITHIN THE STORE FRONTAGE, IT IS COUNTED TOWARD THE |
| TOTAL PERMITTED SIGNAGE |
| |
| D. THE TABLE BELOW PROVIDES THE SIGNAGE PERMITTED AND |
| THE AMOUNT OF SIGNAGE THAT STAFF CAN ACCOUNT FOR. IF NO |
| SIGNAGE IS TO BE REMOVED, THEN IF THE AWNING SIGNAGE |
| EXCEEDS 8.2 SQUARE FEET, THE PROPOSED ARCADE IDENTITY |
| SIGN WILL NEED TO BE REDUCED IN SIZE. |
| |
| PERMITTED: 97.5 SF |
| EXISTING CITY CELLAR FASCIA SIGN: 49.5 SF |
| EXISTING AWING SIGNS: ??? SF |
| APPROVED BARRIO SANGRIA SIGN (PERMIT 19050032): 16.8 SF |
| PROPOSED SIGN: 23 SF |
| |
| TOTAL SIGN AREA: UNKNOWN; EXCLUDING AWNING SQUARE |
| FOOTAGE 89.3 SF |
| |
| 3) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA REQUIRE ALL LIGHTING CONDUIT, WIRING, BALLAST |
| BOXES, TRANSFORMERS, AND OTHER EQUIPMENT NECESSARY FOR |
| SIGN CONNECTION SHALL BE CONCEALED AND NOT VISIBLE TO |
| THE PUBLIC. THE PROPOSED SIGN LIGHTING HAS AN EXPOSED |
| BELL BOX WITH DISCONNECT SWITCH AND ELECTRICAL LEAD |
| WITHIN FLEXIBLE CONDUIT, WHICH IS NOT PERMITTED. |
| ADDITIONALLY, NO INFORMATION IS PROVIDED AS TO HOW THE |
| ELECTRIC SERVICE IS PROVIDED TO THE BELL BOX. YOU ARE |
| SHOWING THE LIGHTING AS PART OF THIS PERMIT, SO IN |
| ACCORDANCE WITH THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA YOU NEED TO PROVIDE THE INFORMATION ON HOW THE |
| CONCEALMENT REQUIREMENT IS MET. YOU ARE NOT ALLOWED TO |
| DESIGN A SIGN WITH THE WIRING STUBBED OUT THAT THEN |
| REQUIRES NON-COMPLIANCE WITH THE CONCEALMENT |
| REQUIREMENT. IN THIS SPECIFIC CASE YOU MAY NOT REMOVE |
| THE ITEMS WHICH DID NOT COMPLY WITH THE ROSEMARY SQUARE |
| TENANT SIGN CRITERIA AND SIMPLY STATE IT WILL BE |
| PROVIDED WITH OTHERS. YOU NEED TO COORDINATE WITH THE |
| "OTHERS" WHO ARE PROVIDING THE ELECTRICAL PRIMARY AND |
| PROVIDE THIS INFORMATION ON THE PLANS TO VERIFY THAT |
| THE CONCEALMENT REQUIREMENTS ARE MET. |
| |
| 4) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA REQUIRE THAT RIVETS, SCREWS AND OTHER |
| FASTENERS THAT EXTEND TO VISIBLE SURFACES SHALL BE |
| FLUSH, FILLED AND FINISHED SO AS TO BE UNNOTICEABLE. |
| THE BOLT HEADS, BOLT ENDS AND NUTS THAT EXTEND PAST THE |
| MOUNTING HARDWARE DO NOT MEET THIS STANDARD. IF THE |
| BOLT HEADS MUST EXTEND PAST THE MOUNTING HARDWARE, THEY |
| NEED TO BE CONCEALED BY CAPS MATCHING THE COLOR OF THE |
| MOUNTING HARDWARE. |
| |
| 5) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN |
| CRITERIA ALLOW A MAXIMUM HEIGHT FOR ARCADE IDENTITY |
| SIGNS OF 12 FEET FROM THE FINISHED FLOOR. THE SIGN |
| EXCEEDS THE 12 FOOT HEIGHT ALLOWANCE. 9 FEET + 4 FEET 8 |
| INCHES = 13 FEET 8 INCHES. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |