2020-01-30 06:47:33 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 |
| SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT |
| OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & |
| TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME |
| SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING |
| DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. |
| FBC-EC 405.2.5. PROVIDE CORRECTION. |
| |
| 2. PROVIDE ELECTRICAL DRAWING SHOWING CONDUIT, WIRE |
| SIZE, CIRCUIT NUMBER AND PANEL WHERE CIRCUIT IS FED |
| FROM. FBC 107.2.1 |
| |
| 3. THE VALUE FOR SITE LIGHTING IS NOT TO BE INCLUDED IN |
| THE MAIN PERMIT REVIEW. PLEASE CONTACT SAMANTHA HILL |
| (CHIEF PLANS EXAMINER) @ [email protected] WITH A COPY OF |
| THE ELECTRICIAN'S CONTRACT AND THE GENERAL CONTRACTOR'S |
| CONTRACT TO VERIFY THE PROPER FEES HAVE BEEN COLLECTED. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |