Plan Review Notes
Plan Review Notes For Permit 20010255
Permit Number 20010255
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-03-02 15:30:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE EXISTING BUILDING IS PROTECTED BY FIRE
 SPRINKLERS. ANY OVERHANG OR CANOPY IS REQUIRED TO HAVE
 THE FIRE SPRINKLER SYSTEM EXTENDED TO PROTECT IT.
  
 ADDITIONALLY, A CURTAIN IS PROPOSED THAT ENCLOSES THE
 CANOPY.
  
  
 8.15.7* EXTERIOR PROJECTIONS.
 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3,
 OR
 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER
 EXTERIOR
 PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH.
 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 WHERE
 THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS
 THAT
 ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE
 RETARDANT?
 TREATED WOOD AS DEFINED IN NFPA 703.
  
 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER EXTERIOR
 PROJECTIONS
 GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS WHERE
 COMBUSTIBLES
 ARE STORED.
  
 PLEASE REVIEW, CORRECT AND PROVIDE AN APPLICABLE NOTE
 THAT THE SPRINKLER WORK SHALL BE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
  
  
 2) PLEASE PROVIDE A DETAILE DNARRATIVE OF HOW THIS
 CREATED SPACE IS PROPOSED TO FUNCTION.
  
  
 3) A CURTAIN IS INDICATED, WAS THE MATERIAL OF THE
 CURTAIN PROVIDED.
  
 IT IS NOT CLEAR WHAT THE CURTAIN IS COMPOSED OF.
  
 PLEASE PROVIDE A SAMPLE AND OR MANUFACTURES SPECS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  