Plan Review Notes For Permit 20010255 |
Permit Number |
20010255 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-03-02 15:30:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE EXISTING BUILDING IS PROTECTED BY FIRE | | SPRINKLERS. ANY OVERHANG OR CANOPY IS REQUIRED TO HAVE | | THE FIRE SPRINKLER SYSTEM EXTENDED TO PROTECT IT. | | | | ADDITIONALLY, A CURTAIN IS PROPOSED THAT ENCLOSES THE | | CANOPY. | | | | | | 8.15.7* EXTERIOR PROJECTIONS. | | 8.15.7.1 UNLESS THE REQUIREMENTS OF 8.15.7.2, 8.15.7.3, | | OR | | 8.15.7.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER | | EXTERIOR | | PROJECTIONS EXCEEDING 4 FT (1.2 M) IN WIDTH. | | 8.15.7.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED | | WHERE | | THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH MATERIALS | | THAT | | ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, OR FIRE | | RETARDANT? | | TREATED WOOD AS DEFINED IN NFPA 703. | | | | 8.15.7.5* SPRINKLERS SHALL BE INSTALLED UNDER EXTERIOR | | PROJECTIONS | | GREATER THAN 2 FT (0.6 M) WIDE OVER AREAS WHERE | | COMBUSTIBLES | | ARE STORED. | | | | PLEASE REVIEW, CORRECT AND PROVIDE AN APPLICABLE NOTE | | THAT THE SPRINKLER WORK SHALL BE UNDER SEPARATE PERMIT | | AND SHOP DRAWINGS. | | | | | | | | 2) PLEASE PROVIDE A DETAILE DNARRATIVE OF HOW THIS | | CREATED SPACE IS PROPOSED TO FUNCTION. | | | | | | 3) A CURTAIN IS INDICATED, WAS THE MATERIAL OF THE | | CURTAIN PROVIDED. | | | | IT IS NOT CLEAR WHAT THE CURTAIN IS COMPOSED OF. | | | | PLEASE PROVIDE A SAMPLE AND OR MANUFACTURES SPECS. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|