Plan Review Notes
Plan Review Notes For Permit 20010253
Permit Number 20010253
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-01-14 12:30:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS ONLY 1 PLAN SHEET AND 1 SET OF MANUFACTURES
 SPECIFICATION SHEETS.
  
 A MINMIMU OF 2 SETS ARE REQUIRED.
  
 PLEASE PROVIDE REVIEW AND PROVIDE.
  
  
 2) THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP
 PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM
 OVER.
  
 THERE IS NO HYDRAULIC CALCULATION SUBMITTED THAT SHOWS
 THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE
 EXISTING SYSTEM DESIGN.
  
 PLEASE PROVIDE CALCULATIONS DETAILS OR PROVIDE A
 STATEMENT/REVIEW BY THE EOR THAT THE FLEXHEADS WILL NOT
 PROVIDE A NEGATIVE IMPACT ON THE CURRENT DESIGN AND
 THAT THE SYSTEM WILL FUNCTION AS ORGINALLY DESIGNED.
  
  
  
 3) THERE IS NO CEILING GRID DETAIL OR SPEC SHEETS THAT
 WILL SUPPORT THE NEW FLEX DROPS. THE DRAWING IS VERY
 LIMITED WITH NO SPEC SHEET BACKUP.
  
 PLEASE PROVIDE GREATER DETAIL AND SPEC SHEETS FOR THE
 BRACKET AND GRID.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved