Plan Review Notes For Permit 20010253 |
Permit Number |
20010253 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-01-14 12:30:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS ONLY 1 PLAN SHEET AND 1 SET OF MANUFACTURES | | SPECIFICATION SHEETS. | | | | A MINMIMU OF 2 SETS ARE REQUIRED. | | | | PLEASE PROVIDE REVIEW AND PROVIDE. | | | | | | 2) THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP | | PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM | | OVER. | | | | THERE IS NO HYDRAULIC CALCULATION SUBMITTED THAT SHOWS | | THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE | | EXISTING SYSTEM DESIGN. | | | | PLEASE PROVIDE CALCULATIONS DETAILS OR PROVIDE A | | STATEMENT/REVIEW BY THE EOR THAT THE FLEXHEADS WILL NOT | | PROVIDE A NEGATIVE IMPACT ON THE CURRENT DESIGN AND | | THAT THE SYSTEM WILL FUNCTION AS ORGINALLY DESIGNED. | | | | | | | | 3) THERE IS NO CEILING GRID DETAIL OR SPEC SHEETS THAT | | WILL SUPPORT THE NEW FLEX DROPS. THE DRAWING IS VERY | | LIMITED WITH NO SPEC SHEET BACKUP. | | | | PLEASE PROVIDE GREATER DETAIL AND SPEC SHEETS FOR THE | | BRACKET AND GRID. | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|