2020-02-20 06:40:101) THERE ARE TWO DIFFERENT GAS PLANS IN THIS PERMIT
 APPLICATION FILE AND I DON'T KNOW WHICH ONE IS THE
 CORRECT ONE TO BE USED FOR THIS PERMIT. SUBMIT TWO
 COMPLETE COPIES OF A GAS PLAN FOR REVIEW. WPB AMEND. TO
 FBC SEC. 107.1.
 2) SUBMIT TWO COPIES OF THE MANUAL FOR THE POOL HEATER.
 WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT DETAILS FOR THE MAKEUP AIR FOR THE DRYER. HOW
 ARE SUPPLYING THE AIR, THROUGH A DUCT, LOUVER, ETC.? BE
 SPECIFIC. IF USING A LOUVER, SHOW THE SIZE, SQUARE INCH
 AREA, ETC. PER THE 2017 FBC-FUEL GAS CODE SEC.304.1,
 614.6 (CLOTHES DRYERS) OR 2017 FBC-RES. SEC.G 2407.1
 AND G2439.4 (CLOTHES DRYERS).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW