Plan Review Notes For Permit 20010149 |
Permit Number |
20010149 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-02-20 06:40:10 | 1) THERE ARE TWO DIFFERENT GAS PLANS IN THIS PERMIT | | APPLICATION FILE AND I DON'T KNOW WHICH ONE IS THE | | CORRECT ONE TO BE USED FOR THIS PERMIT. SUBMIT TWO | | COMPLETE COPIES OF A GAS PLAN FOR REVIEW. WPB AMEND. TO | | FBC SEC. 107.1. | | 2) SUBMIT TWO COPIES OF THE MANUAL FOR THE POOL HEATER. | | WPB AMEND. TO FBC SEC. 107.2.1. | | 3) SUBMIT DETAILS FOR THE MAKEUP AIR FOR THE DRYER. HOW | | ARE SUPPLYING THE AIR, THROUGH A DUCT, LOUVER, ETC.? BE | | SPECIFIC. IF USING A LOUVER, SHOW THE SIZE, SQUARE INCH | | AREA, ETC. PER THE 2017 FBC-FUEL GAS CODE SEC.304.1, | | 614.6 (CLOTHES DRYERS) OR 2017 FBC-RES. SEC.G 2407.1 | | AND G2439.4 (CLOTHES DRYERS). | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|