Plan Review Notes
Plan Review Notes For Permit 20010135
Permit Number 20010135
Review Stop M
Sequence Number 1
Notes
Date Text
2020-01-08 09:41:031ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010135
 1/8/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ORIGINAL PLANS FOR THE PROPOSED PROJECT WERE
 SUBMITTED ELECTRONICALLY UNDER PERMIT #19070067. THE
 REVISED PLANS ARE PAPER SUBMITTALS THAT DO DO BEAR THE
 ENGINEER'S SIGNATURE AND SEAL AS REQUIRED BY FL.
 STATUTE 471.025 AND SECTION 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE. PLEASE RESUBMIT THE REVISED PLANS
 ELECTRONICALLY.
  
 2) THE REVISION APPLICATION INDICATES 37 NEW VAV BOXES,
 HOWEVER THE PLANS ARE INDICATING 20. PLEASE CLARIFY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved