2020-01-14 18:12:27RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL10497-R6
 SUBMITTED: SELECTED ASSEMBLY W-41 ON PAGE 9 OF 22
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES
 (SEC. R301.2.1 FBC-RESIDENTIAL). IF THE BONDED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES,
 THEN IT CAN NOT BE USED. SEE LIMITATION #5.8 ON PAGE 4
 OF 5. IT DOESN'T ALLOW RATIONAL ANALYSIS ON THESE
 SYSTEMS.
 NEED TO SPECIFY ANOTHER BONDED ASSEMBLY THAT MEET THE
 DESIGN PRESSURES FOR ALL ROOF ZONES. NOTE: THIS
 BUILDING IS LOCATED IN EXPOSURE D AND IT LOOKS LIKE
 ASSEMBLY W-42 WILL MEET THE DESIGN PRESSURES FOR ALL
 ROOF ZONES.
 PLEASE ADVICE IF INSTALLING ASSEMBLY W-42 OR SPECIFY
 ANOTHER ASSEMBLY.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
 FAC 61G20-3.001.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]