Plan Review Notes
Plan Review Notes For Permit 20010101
Permit Number 20010101
Review Stop M
Sequence Number 1
Notes
Date Text
2020-01-24 15:22:071ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010101
 1/24/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1-01: PROVIDE AC COOLING AND HEATING
 CALCULATIONS FOR THE NEW AC SYSTEM- SECTION R403.6.1
 FBC EC.
  
 2) M1-01: SUBMIT AN ENERGY COMPLIANCE REPORT- SEE
 SECTIONS R101.5 & R503.2 FBC EC. CHANGE IN SPACE
 CONDITIONING.
  
 3) M1-01: PROVIDE ENGINEERING FOR THE NEW CONDENSER AND
 MOUNTING PAD INSTALLATIONS- SECTIONS M1305.1.4.1 &
 M1401.4 FBC RES.
  
 ANY NONCONDITIONED OR LOW-ENERGY SPACE THAT IS ALTERED
 TO BECOME CONDITIONED SPACE SHALL BE REQUIRED TO BE
 BROUGHT INTO FULL COMPLIANCE WITH THIS CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  