Notes |
Date |
Text |
2020-01-03 16:26:02 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW DENIED: | | | | FBC B 107, THE SELECTED OPTION SELECTED (W-5) ON PAGE | | 14 IN THE NEMO EVALUATION REPORT DOES NOT MEET THE | | REQUIRED PRESSURESFOR EXPOSURE C. SELECT A DIFFERENT | | OPTION THAT WILL MEET THE REQUIRED PRESSURES AS SHOWN | | ON PAGE 3 OF THE SAME REPORT. |
|