2020-02-13 09:17:12FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) THIS PROJECT WAS SUPPOSED TO BE BROKEN UP INTO THREE
 (3) SPEARATE PERMITS BECAUSE OF THE ELECTRICAL SERVICE
 AREAS "A", "B", AND "C"
  
 2) THE AVAILABLE FAULT CURRENT SHALL BE CALCULATED FOR
 THE SERVICE IN CONJUNCTION WITH THE AVAILABLE FAULT
 FROM FPL AT THE TRANSFORMER.
  
 110.24 AVAILABLE FAULT CURRENT
 ( A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN
 DWELLING UNITS SHALL BE LEGIBLY MARKED IN THE FIELD
 WITH THE MAXIMUM
 AVAILABLE FAULT CURRENT. THE FIELD MARKING(S) SHALL
 INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS
 PERFORMED AND BE OF SUFFICIENT
 DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.