Plan Review Notes For Permit 20010094 |
Permit Number |
20010094 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-02-13 09:17:12 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) THIS PROJECT WAS SUPPOSED TO BE BROKEN UP INTO THREE | | (3) SPEARATE PERMITS BECAUSE OF THE ELECTRICAL SERVICE | | AREAS "A", "B", AND "C" | | | | 2) THE AVAILABLE FAULT CURRENT SHALL BE CALCULATED FOR | | THE SERVICE IN CONJUNCTION WITH THE AVAILABLE FAULT | | FROM FPL AT THE TRANSFORMER. | | | | 110.24 AVAILABLE FAULT CURRENT | | ( A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN | | DWELLING UNITS SHALL BE LEGIBLY MARKED IN THE FIELD | | WITH THE MAXIMUM | | AVAILABLE FAULT CURRENT. THE FIELD MARKING(S) SHALL | | INCLUDE THE DATE THE FAULT-CURRENT CALCULATION WAS | | PERFORMED AND BE OF SUFFICIENT | | DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. |
|