Plan Review Notes
Plan Review Notes For Permit 20010092
Permit Number 20010092
Review Stop E
Sequence Number 1
Notes
Date Text
2020-02-06 20:25:13ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. DESIGNS OVER $125,000 MUST BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL. F.S.
 471.003(2)(H)(1)
  
 2. PROVIDE UL OR OTHER NRTL (NATIONALLY RECOGNIZED
 TESTING LABORATORY) LISTINGS FOR ALL
 DEVICES/MATERIALS/AND EQUIPMENT. LIGHT FIXTURES, LIGHT
 POLES, ETC. NEC 90.7, 110.2, 110.3 FBC 107.2.1
  
 3. FBC-107.1 GENERAL - FAC 61G15-23.002 - PROVIDE A
 TITLE BLOCK FOR THE ENGINEER OF RECORD CONSISTENT WITH
 THE REQUIREMENTS OF THIS SECTION, E.G.: FIRM NAME,
 LICENSE NUMBER, PHONE NUMBER...ETC.
  
 4. ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS.
 FBC-EC 405.2.5 (A NOTE ON PLAN WILL SUFFICE).
  
 5.PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 6.PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE
 MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24. LABELS OUTDOORS MUST BE
 SUFFICIENT TO WITHSTAND THE WEATHER AND ELEMENTS.
  
 7.PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER