Plan Review Notes For Permit 20010077 |
Permit Number |
20010077 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-01-08 14:27:56 | 1) THE GAS SIZING TABLE THAT HAS BEEN SUBMITTED IS FROM | | AN OUTDATED GAS CODE EDITION. SUBMIT THE CORRECT SIZING | | FROM THE 2017 FBC-GAS CODE. | | 2) SHOW THE DISTANCE FROM THE GAS METER TO THE POOL | | HEATER. | | 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE GAS REGULATOR TO BE INSTALLED AT | | THE POOL HEATER. | | 4) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD | | OF EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC. 409.4. | | 5) WHERE CONNECTED TO RIDGID PIPING, A UNION SHALL BE | | INSTALLED WITHIN ONE FOOT OF EITHER SIDE OF THE | | REGULATOR. 2017 FBC-FUEL GAS SEC.410.2(7). | | 6) THE GAS PLAN ON FILE WITH THE CITY SHOWS THE BTU | | LOAD OF THE EXISTING GAS RANGE AS 125,000 BTU'S AND THE | | WATER HEATER AT 255,000 BTU'S. CLARIFY. | | 7) THE GAS PLANS REFERENCE NFPA 58. THIS STANDARD IS | | FOR LP GAS. CLARIFY. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|