Date |
Text |
2020-01-07 08:47:08 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| NFPA 99 = HEALTH CARE FACILITIES CODE |
| NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW |
| |
| PLUMBING COMMENTS: DENIED |
| 1. PLAN SHEET A-2: SANITARY RISER; BATHTUB FIXTURE |
| DRAIN SHALL CONNECT TO THE HORIZONTAL WET VENT UPSTREAM |
| OF THE SINK CONNECTION TO COMPLY WITH FBC RES P3108.1. |
| 2. PLAN SHEET A-2: SANITARY RISER; HORIZONTAL DRAIN |
| SERVICING THE WASHER IS SIZED 2 INCH BY THE DESIGNER |
| AND HAS BEEN MODIFIED BY HAND TO REFLECT 3 INCH SIZE. |
| PER WPB FBC 107.2.1, REVISE TO REFLECT 3 INCH SIZE. |
| NOTE THAT MOST MANUFACTURER?S RECOMMENDATIONS DO |
| REQUIRE THAT THE DRAIN BE 3 INCH. |
| 3. PLAN SHEET A-2: SANITARY RISER AND PLAN VIEW; |
| PROVIDE A CLEANOUT AT OR NEAR THE JUNCTION OF THE |
| BUILDING DRAIN AND BUILDING SEWER TO COMPLY WITH FBC |
| RES P3005.2.3. |
| 4. PLAN SHEET A-2: NOTE 11; SELECTED WATER HEATER |
| PROVIDES A MAXIMUM OF 3.1 GPM. THIS APPEARS NOT TO |
| SATISFY THE REQUIREMENTS FOR HOT WATER FOR THE FIXTURES |
| REQUIRING HOT WATER. PER WPB FBC 107.2.1, PROVIDE |
| CALCULATIONS FOR THE HOT WATER DEMAND AND INSURE THAT |
| THE SELECTED WATER HEATER WILL SATISFY THE |
| REQUIREMENTS. |
| 5. PER THE WPB UTILITIES DEPTMENT, A RPZ BACKFLOW |
| PREVENTOR SHALL BE INSTALLED AT THE WATER SERVICE TO |
| THE PROPERTY COMPLYING WITH WPB CCCM. PER WPB FBC |
| 107.2.1, PROVIDE NOTE ON PLAN SHEET A-1 AND A-2. |
| 6. SUBMIT TWO COPIES OF A SLAB REPAIR DETAIL FOR |
| REVIEW. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM |
| THICKNESS OF THE CONCRETE TO BE REPLACED AND THE PSI OF |
| THE CONCRETE. SHOW SIZE AND LENGTH OF DOWELS, THE |
| MINIMUM DEPTH INTO EXISTING SLAB, ANCHORING MATERIAL |
| FOR DOWELS AND THE SPACING OF THE DOWELSON CENTER. THE |
| REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL |
| AND THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED |
| SOIL. A COPY OF THE TERMITE CERTIFICATION SHALL BE |
| ONSITE FOR THE FINAL INSPECTION. REFER TO FBC RES |
| R318.1.1, R402.2, R404.1.3.3.7.1, R501.2, R506.1 AND |
| R506.2.3. |
| |
| |
| |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| GAS COMMENTS: |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 20010067 747 ARDMORE RD |
| |