2020-03-05 15:51:54SIGN SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- ENGINEERED DRAWINGS ARE INCOMPLETE. FRONT ELEVATION
 W/ CAISSON FOUNDATION DETAIL 1 ON DRAWING #1 STATES
 THAT "SIGN CABINETS, BASE AND CONNECTIONS TO POLE BY
 SIGNS UNLIMITED-NC" SIGN ENGINEER OF RECORD NEEDS TO
 PROVIDE COMPLETE INFORMATION FOR THE CONSTRUCTION AND
 PROPOSED INSTALLATION OF THE SIGN CABINET AND BASE.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. 1609.1 FBC-BUILDING.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. SAME PLANS SUBMITTED.
 NOTE; THIS COMMENT APPLIES TO SIGN SHOWN ON DRAWING #5
 ALSO. ENGINEER NEEDS TO SPECIFY THE FASTENING OF THE
 WALL SIGN NOT SIGNS UNLIMITED.
  
  
 ORIGINAL COMMENT:
 2- PLANS NEED TO SPECIFY THE LOCATION OF EACH OF THE
 SIGNS SHOWN ON THE ENGINEERED DRAWINGS 1 THRU 6.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. 1609.1 FBC-BUILDING.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. SAME PLANS SUBMITTED.
  
 ORIGINAL COMMENT:
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. PROVIDE COPY OF SIGNED CONTRACTS INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 RESPONSE.
 REPEAT COMMENT. NOT ADDRESSED.
  
 4- NOTICE OF COMMENCEMENT WILL BE REQUIRED. SEC. 713.13
 F.S.
  
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,